Plan Review Notes
Plan Review Notes For Permit 13050004
Permit Number 13050004
Review Stop B
Sequence Number 3
Notes
Date Text
2013-06-20 16:50:31BUILDING PLAN REVIEW
 PERMIT: 13050004
 ADD: 1701 S FLAGLER # 1502
 CONT: MARYJULI CONSTRUCTION
 TEL: (561)386-6032
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
 DATE: JUNE 20/2013
 ACTION:BUILDING PROVISO
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) TILE, MARBLE FLOORS OR SIMILAR MATERIALS, 2010 FBC-B
 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES
 BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A
 PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE
 AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE
 WITH ASTM E 492.
  
 2) 2010 FBC-B 603.2EXCEPTION # 1. INSULATION PLACED
 BETWEEN TWO LAYERS OF NONCOMBUSTIBLE MATERIALS WITHOUT
 AN INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 100.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  