2013-06-11 07:59:46BUILDING PLAN REVIEW
 PERMIT: 13050004
 ADD: 1701 S FLAGLER # 1502
 CONT: MARYJULI CONSTRUCTION
 TEL: (561)386-6032
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: JUNE 11/2013
 ACTION: DENIED
  
 1) SEMI-COMPLIED. ENGINEERING EXPRESS HAS PROVIDED WIND
 DESIGN FOR HIGH RISE, FOR AN EXPOSURE D, THE END ZONE
 IS LABELED 3'-0". THIS UNIT WHICH IS AN END UNIT HAS
 ANOTHER UNIT BEHIND IT THE LEAST HORIZONTAL DIMENSION
 OF UNIT WHEN DOUBLED IS 68 FEET WIDE, 10 % OF THE LEAST
 DIMENSION WOULD BE 6'-8" (END ZONE), WINDOW MARK # 4
 WOULD BE LOCATED IN A END ZONE WITH HIGHER PRESSURES.
  
  
 2) 2ND REQUEST, 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. SLIDERS AND SWING DOOR OK.
 (B) WINDOWS PLEASE CIRCLE TYPE OF GLASS TO BE ORDERED,
 NOTE ONLY ONE WILL WORK!!!!!!
 (B) MULLIONS PLEASE CIRCLE TYPE OF ANCHOR TO BE
 INSTALLED, NOTE TABLE 7 OF 22 THE FORMULA SHOWN ON THIS
 SHEET HAS TO BE COMPLETED TO COMPLETED TO CONVERT TO
 PRESSURES FOR BOTH THE MULLION AND FASTENERS.
  
 4A) COMPLIED. TILE MARBLE FLOORS OR SIMILAR MATERIALS,
 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.
  
 4B) 2ND REQUEST, PROTECTO WRAP. SPEC SHEET HAS NO DATA
 ON FLAME SPEAD. TILE MARBLE OR SIMILAR MATERIALS: 2010
 FBC-B 603.2EXCEPTION # 1. INSULATION PLACED BETWEEN TWO
 LAYERS OF NONCOMBUSTIBLE MATERIALS WITHOUT AN
 INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 100.
  
 5-6) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676