2013-05-06 12:41:30FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 PENDING :
  
 PLEASE SEE BUILDING REVIEW COMMENTS ON ACCESSIBILITY.
  
 ***NOTE***
 TWO DRINKING FOUNTAINS ARE SHOWN AS EXISTING. IF THESE
 ARE SET AT WHEELCHAIR HEIGHT, THE NEW DRINKING FOUNTAIN
 SHOULD BE A HI/LO DRINKING FOUNTAIN PER ACCESSIBILITY
 211.2 OR A SINGLE FOUNTAIN SET AT A HEIGHT TO COMPLY
 WITH ACCESSIBILITY 602.7
  
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  