2013-05-04 08:54:25400 CLEMATIS STREET - SUITE #101
 PERMIT #13041140
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PARTIAL CHANGE OF OCCUPANCY FROM MERCANTILE
 (RESTAURANT) TO ASSEMBLY*****
  
 THE PERMIT APPLICATION INCORRECTLY INDICATES THE
 ADDRESS AS "NORTH" CLEMATIS STREET.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING OCCUPANT LOADS, EXIT
 SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON
 PATH OF TRAVEL ETC.
  
 EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM
 OF 1-1/2 HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 50 OR
 MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS
 TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES
 ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE.
  
 NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. PER FBC
 SECTION 907.1.1 CONSTRUCTION DOCUMENTS - "CONSTRUCTION
 DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE, THE FLORIDA
 FIRE PREVENTION CODE, AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL."
  
 NOTE: SEPARATE PLANS AND SUB-PERMITS ARE REQUIRED FOR
 THE MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  