2013-06-14 10:26:492010 FBC / 2008 NEC
  
 ALL ELECTRICAL WORK SHALL COMPLY WITH THE 2008 NATIONAL
 ELECTRICAL CODE
  
 1) NEW PANEL AND CIRCUIT BREAKERS SHALL COMPLY WITH THE
 2008 NEC.
  
 2) ARC-FAULT PROTECTION (COMBINATION TYPE) IS REQUIRED
 TO COMPLY WITH NEC 210.12B.
  
 3) MULTIWIRE BRANCH CIRCUITS SHALL COMPLY WITH NEC
 210.4.
2013-06-13 10:55:26NEW DRAWINGS SUBMITTED. JG.