Plan Review Notes
Plan Review Notes For Permit 13041131
Permit Number 13041131
Review Stop B
Sequence Number 2
Notes
Date Text
2013-06-13 11:26:39BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE THE ENERGY CALCULATIONS: A) ITEM #15 IS
 TAKING THE "CV" CREDIT. PLANS NEED TO SHOW COMPLIANCE.
 B) BUILDING ORIENTATION NEEDS TO MATCH SURVEY. C)
 COMPLETE ALL THE INFORMATION ON TOP OF FORM.
  
 2- PROVIDE PRODUCT APPROVAL FOR STORAGE BARN TYPE DOORS
 AS SHOWN ON PLANS. AND, ENGINEER OF RECORD TO
 REVIEW/APPROVE IT BEFORE SUBMITTAL.
  
 3- REVISE ALL ROOF SHEATHING SPECIFICATIONS SHOWN ON
 ALL NOTES AND DETAILS. PROVIDE COMPLETE ENGINEERING
 ANALYSIS FOR ALT. METHOD SPECIFIED ON THE LAST SENTENCE
 OF SPECIFICATIONS OR DELETE THE ALT. METHOD.
  
  