Plan Review Notes For Permit 13041131
Permit Number 13041131
Review Stop M
Sequence Number 1
Notes
Date Text
2013-05-15 11:09:16RESIDENTIAL (R3) ADDITION MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS NEED TO HAVE EQUIPMENT
 MODEL AND NUMBER AS REQUIRED BY SEC. 403.6 OF 2010
 FBC-ENERGY CONSERVATION.
  
 2- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE A/C DESIGN SHOWN ON PLAN. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712