Plan Review Notes
Plan Review Notes For Permit 13041063
Permit Number 13041063
Review Stop B
Sequence Number 1
Notes
Date Text
2013-04-30 16:59:22****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS. IF
 NON COMPLIANT EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 PROPOSED, ALSO NOTE EXISTING CONDITIONS (TYPE OF
 WINDOW) AND EXISTING CLEAR OPENING SIZE AND PROPOSED
 CLEAR OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB
 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN
 5%.
  
 2, REVISE FLOOR PLAN TO INCLUDE TYPE OF WINDOW AT EACH
 LOCATION FBC 107.
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved