2013-04-30 12:06:31 | 1608 SOUTH DIXIE HIGHWAY |
| PERMIT #13040934 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| RESPONSE COMMENT: "GENERAL COMMERCIAL" IS NOT AN |
| OCCUPANCY TYPE. IF THIS PERMIT IS FOR A SHELL PERMIT |
| ONLY WITH NO TENANT PLEASE INDICATE. |
| ORIGINAL COMMENT: PLANS DO NOT INDICATE THE OCCUPANCY |
| TYPE THAT WILL BE OCCUPYING SPACE 3 & 4. |
| |
| RESPONSE COMMENT: PROVIDE DRAWING NOTE INDICATING WALL |
| TO BE PERMANENTLY IDENTIFIED WITH THE NOTE BELOW. |
| EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH |
| SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL |
| OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN |
| HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE |
| SPACED NOT MORE THAN 15 FEET ON CENTER. REFERENCE |
| SECTION 8.3.2.4 OF FLORIDA FIRE PREVENTION CODE - NFPA |
| 101 |
| |
| RESPONSE COMMENT: NO EGRESS INFORMATION PROVIDED FOR |
| SPACE #6. |
| ORIGINAL COMMENT: THE NEW FIRE BARRIER APPEARS TO |
| ELIMINATE AN EXIT FROM SPACE #6. SHOW THE EXIT DOORS |
| AND TRAVEL DISTANCES FOR SPACE #6. |
| |
| RESONSE COMMENT: INDICATE THE EXISTING LOCATIONS AND |
| DIMENSION THE EXISTING SPRINKLER LOCATIONS WITH |
| REFERENCE TO THE NEW PROPOSED WALL TO CONFIRM TO NO |
| SPRINKLER ADDITIONS OR RELOCATIONS ARE REQUIRED. |
| SEPARATE PLANS AND PERMITS ARE NEEDED TO RELOCATE THE |
| EXISTING SPRINKLERS AROUND THE NEW FIRE BARRIER. |
| |