 PERMIT #13040934
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 PLANS DO NOT INDICATE THE OCCUPANCY TYPE THAT WILL BE
 OCCUPYING SPACE 3 & 4.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER. REFERENCE
 SECTION 8.3.2.4 OF FLORIDA FIRE PREVENTION CODE ? NFPA
 101
  
 PROVIDE A UL LISTED WALL ASSEMBLY DETAIL.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. PROVIDE
 PENETRATION PROTECTION DETAILS.
  
 THE NEW FIRE BARRIER APPEARS TO ELIMINATE AN EXIT FROM
 SPACE #6. SHOW THE EXIT DOORS AND TRAVEL DISTANCES FOR
 SPACE #6.
  
 INDICATE THE LOCATION OF EXIT SIGNS, EMERGENCY LIGHTING
 AND FIRE EXTINGUISHERS.
  
 INDICATE ANY DUCTWORK PENETRATING THE NEW FIRE BARRIER.
  
 SEPARATE PLANS AND PERMITS ARE NEEDED TO RELOCATE THE
 EXISTING SPRINKLERS AROUND THE NEW FIRE BARRIER.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  