Plan Review Notes
Plan Review Notes For Permit 13040917
Permit Number 13040917
Review Stop E
Sequence Number 2
Notes
Date Text
2013-07-01 11:02:12 
 13040917
 7000 S DIXIE HWY, SUITE 5
 CHANGE OF USE FROM BUSINESS TO CHURCH
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS. PROVIDE AN PLAN SHOWING THE ELECTRICAL
 SYSTEM. SHOW ALL NEW AND EXISTING ELECTRICAL OUTLETS
 INCLUDING LIGHTING.
  
 VERIFY THAT THE REQUIRED WORKING CLEARANCES AND
 DEDICATED WORKING SPACE HAS BEEN PROVIDED FOR THE
 ELECTRICAL EQUIPMENT AND PANEL BOARDS. NEC 110.26,
 240.24, 408.17
  
 VERIFY THE MEANS OF EGRESS HAS EMERGENCY ILLUMINATION
 AND EXIT SIGNS. FBC 1006.2 1011.1
  
 GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS.
 NEC 422.52
  
 VENDING MACHINES IF PROVIDED SHALL BE PROTECTED WITH
 GFCI?S. NEC 422.51
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS MUST
 BE GFCI PROTECTED. NEC 210.8
  
 NOTE:
 SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE,
 DATA, FIRE ALARM, AND SECURITY.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  
  