Plan Review Notes For Permit 13040917 |
Permit Number |
13040917 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-07-01 11:02:12 | | | 13040917 | | 7000 S DIXIE HWY, SUITE 5 | | CHANGE OF USE FROM BUSINESS TO CHURCH | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. PROVIDE AN PLAN SHOWING THE ELECTRICAL | | SYSTEM. SHOW ALL NEW AND EXISTING ELECTRICAL OUTLETS | | INCLUDING LIGHTING. | | | | VERIFY THAT THE REQUIRED WORKING CLEARANCES AND | | DEDICATED WORKING SPACE HAS BEEN PROVIDED FOR THE | | ELECTRICAL EQUIPMENT AND PANEL BOARDS. NEC 110.26, | | 240.24, 408.17 | | | | VERIFY THE MEANS OF EGRESS HAS EMERGENCY ILLUMINATION | | AND EXIT SIGNS. FBC 1006.2 1011.1 | | | | GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS. | | NEC 422.52 | | | | VENDING MACHINES IF PROVIDED SHALL BE PROTECTED WITH | | GFCI?S. NEC 422.51 | | | | ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS MUST | | BE GFCI PROTECTED. NEC 210.8 | | | | NOTE: | | SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE, | | DATA, FIRE ALARM, AND SECURITY. | | | | | | ROBERT LECKY | | ELECTRICAL PLANS REVIEW | | | | |
|