Plan Review Notes For Permit 13040917 |
Permit Number |
13040917 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-04-26 10:37:25 | FBC 2010 EXISTING BUILDING CODE | | FBC 2010 ACCESSIBILITY CODE | | FBC 2010 PLUMBING REVIEW #1 | | DENIED: | | | | 1. WITH THE CHANGE OF OCCUPANCY TO A3 CHURCH, | | FBC PLUMBING 403.1 MINIMUM PLUMBING FACILITIES: | | A-3 = 1 HI/LO DRINKING FOUNTAIN PER 1,000 (SEE | | ACCESSIBILITY 211.2 FOR THE HI/LO REQUIREMENT). | | 1 SERVICE SINK. | | UPDATE 5/28/13: A MINIMUM OF ONE DRINKING FOUNTAIN | | WOULD BE REQUIRED IF USING THE EXEMPTION OF CHURCHES | | FROM ADA. SS. 553.501-513, F.S. | | | | | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|