Plan Review Notes
Plan Review Notes For Permit 13040917
Permit Number 13040917
Review Stop B
Sequence Number 1
Notes
Date Text
2013-04-30 13:07:36BUILDING PLAN REVIEW
 PERMIT: 13040917
 ADD: 7000 S DIXIE HWY SUITES 6 & 7
 CONT: TBD
 TEL: (561)313-9046
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 4/30/2013
 ACTION: DENIED
  
 NOTE: THE PLANS INDICATE THIS IS A CHANGE OF OCCUPANCY
 FROM A BUSINESS OCCUPANCY TO AN ASSEMBLY (A-3)
 OCCUPANCY. 2010 FBC-EXISTING BUILDING 901.3.1 PARTIAL
 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 912 SHALL APPLY.
  
 1) THE DESIGNER OF RECORD HAS NOT ELECTED TO IDENTIFY
 WHICH OPTION THEY WOULD LIKE TO DESIGN BY:
 912.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT
 SEPARATION.
 912.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH
 SEPARATION.
  
 2) 912.4 MEANS OF EGRESS, GENERAL.
 HAZARD CATEGORIES IN REGARD TO LIFE SAFETY AND MEANS OF
 EGRESS SHALL BE IN ACCORDANCE WITH TABLE 912.4.
 912.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER HAZARD
 CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
 SHOW COMMON PATH OF TRAVEL FBC-B 1014.3 FROM THE
 FURTHEST POINT IN THE PASTORS OFFICE TO THE 36" EXIT,
 IF OVER 75 FEET THEN A 2ND MEANS OF EGRESS IS REQUIRED
 WITH A 32 INCH CLEAR OPENING, MINIMUM OF 2'-10" DOOR.
 2010 FBC-B 1008.1.1.
  
 3) THE SUBMITTED PLAN INDICATES A NEW 36 INCH IMPACT
 DOOR, NO PRODUCT APPROVALS WERE SUBMITTED WILL NEED TO
 COMPLY WITH:
 3A) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3B) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  