2013-04-30 13:07:36 | BUILDING PLAN REVIEW |
| PERMIT: 13040917 |
| ADD: 7000 S DIXIE HWY SUITES 6 & 7 |
| CONT: TBD |
| TEL: (561)313-9046 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: 4/30/2013 |
| ACTION: DENIED |
| |
| NOTE: THE PLANS INDICATE THIS IS A CHANGE OF OCCUPANCY |
| FROM A BUSINESS OCCUPANCY TO AN ASSEMBLY (A-3) |
| OCCUPANCY. 2010 FBC-EXISTING BUILDING 901.3.1 PARTIAL |
| CHANGE OF OCCUPANCY CLASSIFICATION. |
| WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A |
| NEW OCCUPANCY CLASSIFICATION, SECTION 912 SHALL APPLY. |
| |
| 1) THE DESIGNER OF RECORD HAS NOT ELECTED TO IDENTIFY |
| WHICH OPTION THEY WOULD LIKE TO DESIGN BY: |
| 912.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT |
| SEPARATION. |
| 912.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH |
| SEPARATION. |
| |
| 2) 912.4 MEANS OF EGRESS, GENERAL. |
| HAZARD CATEGORIES IN REGARD TO LIFE SAFETY AND MEANS OF |
| EGRESS SHALL BE IN ACCORDANCE WITH TABLE 912.4. |
| 912.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER HAZARD |
| CATEGORY. |
| WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A |
| HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE |
| 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE |
| REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| CODE, BUILDING. |
| SHOW COMMON PATH OF TRAVEL FBC-B 1014.3 FROM THE |
| FURTHEST POINT IN THE PASTORS OFFICE TO THE 36" EXIT, |
| IF OVER 75 FEET THEN A 2ND MEANS OF EGRESS IS REQUIRED |
| WITH A 32 INCH CLEAR OPENING, MINIMUM OF 2'-10" DOOR. |
| 2010 FBC-B 1008.1.1. |
| |
| 3) THE SUBMITTED PLAN INDICATES A NEW 36 INCH IMPACT |
| DOOR, NO PRODUCT APPROVALS WERE SUBMITTED WILL NEED TO |
| COMPLY WITH: |
| 3A) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 3B) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |