2013-06-13 11:50:42BUILDING PLAN REVIEW
 PERMIT: 13040902
 ADD: 411 CLEMATIS ST/ 2ND FLOOR SUITE 230
 CONT: RANDOLPH &DEWDNEY
 TEL: (561)441-1186
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: JUNE 14/ 2013
 ACTION: PROVISO
  
  
  
 BUILDING PROVISO:
 NO TENANT CAN OCCUPY THIS SPACE UNTIL CODE COMPLIANCE
 IS ACHIEVED WITH THESE ITEMS:
  
 1) PLEASE PROVIDE A SCALED PLAN SHOWING COMPLIANCE WITH
 2010 FBC-B 1014.3 EXCEPTION # 1, COMMON PATH OF TRAVEL
 FROM THE FURTHEST POINT IN THE SUITE. PLEASE BE AWARE
 THIS SPACE IS BELIEVED TO HAVE ONLY ONE MEANS OF EGRESS
 INTO AND OUT OF THIS SPACE. TWO ELEMENTS MUST BE IN
 CODE COMPLIANCE, THE FIRST IS COMMON PATH OF TRAVEL
 FROM THE FURHEST POINT, THE SECOND ISSUE IS OCCUPANT
 LOAD, THIS SPACE IS BEING FINISHED AS A WHITE BOX,
 PLEASE REALIZE IF ANY OCCUPANCY OTHER THAN BUSINESS
 LEASES THIS SPACE THE OCCUPANT LOAD WILL BE OVER 49 AND
 REQUIRE 2 MEANS OF EGRESS, 2010 FBC-B TABLE 1015.1.
 WITH THE TWO MEANS OF EGRESS THEY WOULD NEED TO BE
 1/3RD THE DIAGONAL OF THE ROOM APART, 2010 FBC-B
 1015.2.1.
 ON THE 1ST RESUBMISSION OF PLANS THE PLAN INDICATES ONE
 DOOR, WITH THE PLANS NOT DRAWN TO SCALE AND A DIAGONAL
 DISTANCE OF 88 FEET IT WILL APPEAR THAT THE TRAVEL
 DISTANCE WILL BE APPROXIMATELY 111 FEET REQUIRING A
 SECOND DOORWAY, THIS CAN'T BE DETERMINED UNTIL SCALED
 DRAWING WITH DIMENSIONS ARE SUBMITTED FOR REVIEW AND OR
 A FURNITURE PLAN WITH A COMMON PATH OF TRAVEL SHOWN NOT
 EXCEEDING 100 FT.
  
 2) . THE PLANS ALSO DO NOT PROVIDE COMPLIANCE WITH:
 2010 FBC-B 1006.3.1 EXITS SHALL BE MARKED BY AN
 APPROVED SIGN READILY VISIBLE FROM ANY DIRECTION OF
 EXIT ACCESS. EVERY EXIT SIGN SHALL BE SUITABLY
 ILLUMINATED BY A RELIABLE LIGHT SOURCE. EXTERNALLY AND
 INTERNALLY ILLUMINATED SIGNS SHALL BE VISIBLE IN BOTH
 NORMAL AND EMERGENCY LIGHTING.
  
 3) 2ND REQUEST. 1006.3.4 EXIT STAIR DOOR OR TACTILE
 SIGNAGE. TACTILE SIGNAGE STATING ?EXIT? AND COMPLYING
 WITH ICC/ANSI A117.1, AMERICAN NATIONAL STANDARD FOR
 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES, SHALL
 BE INSTALLED ADJACENT TO THE LATCH SIDE OF THE DOOR 60
 INCHES (1524 MM) ABOVE THE FINISHED FLOOR TO THE CENTER
 LINE OF THE SIGN.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved