Date Text
2013-04-27 18:48:55411 CLEMATIS STREET
 PERMIT #13040902
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO SUITE NUMBER PROVIDED ON PERMIT APPLICATION OR
 DRAWINGS.
  
 A NEW FIRE-RATED WALL APPEARS TO BE NEEDED BETWEEN
 TENANT SPACE #D2.107 AND SPACE #D2.202. PROVIDE A WALL
 DETAIL.
  
 PLANS DO NOT INDICATE IF ANY DUCTWORK WILL BE PASSING
 THROUGH THE NEW TENANT SEPARATION WALL.
  
 PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE
 AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 PER SECTION 8.3.5.1, PENETRATIONS THROUGH A FIRE-RATED
 WALL ASSEMBLY SHALL BE PROTECTED BY A FIRESTOP SYSTEM
 OR DEVICE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  