2013-04-29 09:13:07BUILDING PLAN REVIEW
 PERMIT: 13040768
 ADD:777 S FLAGLER # 140E
 CONT: BUTLER CONSTRUCTION CO.
 TEL: (561)832-9700
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 4-29/2013
 ACTION: BUILDING PROVISO
  
 1) EXISTING GLASS DOORS BETWEEN THE VESTIBULE 100 &
 RECEPTION ROOM 101 SWING THE WRONG WAY TO BE CONSIDERED
 PART OF AN EXIT. THE COVERSHEET HAS AN EXIT LIGHT
 DIRECTLY ABOVE THESE DOORS, TO MAKE THIS A CODE
 COMPLIANT ELEMENT EITHER:
 1) REMOVE THE EXIT LIGHT ABOVE THE GLASS DOORS, IS NOT
 REQUIRED TO BE A MEANS OF EGRESS OR,
 2) REVERSE THE SWING OF THE DOORS TO OUT SWING DOORS.
 2010 FBC-B 1008.1.2 DOOR SWING- DOORS SHALL SWING IN
 THE DIRECTION OF EGRESS TRAVEL WHERE SERVING AN
 OCCUPANT LOAD OF 50 OR MORE PERSONS OR A GROUP H
 OCCUPANCY.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676