Plan Review Notes For Permit 13040744 |
Permit Number |
13040744 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-04-23 07:01:05 | NO MECHANICAL SHOWN TO INDICATE EXISTING OR NEW. | | PLUMBING NOT SHOWN, GAS WATER HEATER SHOWN WITHOUT | | INDICATION AS TO EXISTING OR NEW | | PROVIDE ENERGY CODE CALCS | | SMOKE DETECTOR NOT PERMITTED ON BATH CICUIT AS CALLED | | FOR - 210.11C | | LOAD CALC DOES NOT MATCH PANEL SCHEDULE | | WIRE SIZING TO BE PER TABLE 310-16, UNLESS EXCEPTIONS | | APPLY | | REVIEW STOPPED |
|