Plan Review Notes
Plan Review Notes For Permit 13040744
Permit Number 13040744
Review Stop E
Sequence Number 1
Notes
Date Text
2013-04-23 07:01:05NO MECHANICAL SHOWN TO INDICATE EXISTING OR NEW.
 PLUMBING NOT SHOWN, GAS WATER HEATER SHOWN WITHOUT
 INDICATION AS TO EXISTING OR NEW
 PROVIDE ENERGY CODE CALCS
 SMOKE DETECTOR NOT PERMITTED ON BATH CICUIT AS CALLED
 FOR - 210.11C
 LOAD CALC DOES NOT MATCH PANEL SCHEDULE
 WIRE SIZING TO BE PER TABLE 310-16, UNLESS EXCEPTIONS
 APPLY
 REVIEW STOPPED