Date |
Text |
2013-04-20 10:19:32 | 3620 SOUTH DIXIE HIGHWAY |
| PERMIT #13040646 |
| MASTER #13020612 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| PRIVATE FIRE MAINS AND PRIVATE FIRE HYDRANTS FALL UNDER |
| THE BUILDING/FIRE DEPARTMENT JURISDICTION AND ARE |
| REGULATED BY THE REQUIREMENTS OF NFPA 24; THEREFORE, |
| THESE DOCUMENTS MUST BE SIGNED AND SEALED BY THE |
| PROFESSIONAL ENGINEER WHO PREPARED THE DRAWINGS. |
| |
| FIRELINE BACKFLOW PREVENTERS SHALL BE SUPERVISED BY A |
| CHAIN W/ LOCK AND ELECTRONICALLY MONITORED TAMPER |
| SWITCHES. |
| |
| THE MAIN DRIVE INTO/OUT OF THE COMPLEX IS A FIRE LANE. |
| FIRE LANES SHALL HAVE A SURFACE DESIGNED TO ACCOMMODATE |
| FIRE APPARATUS WEIGHING AT LEAST 32 TONS. ACCESS ROADS |
| SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 |
| FEET AND AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS |
| THAN 13 FEET 6 INCHES PER SECTION 18.2.3.4.1.1 OF THE |
| FLORIDA FIRE PREVENTION CODE - NFPA 1 UNIFORM FIRE |
| CODE. |
| |
| FIRE LANES SHALL HAVE PAINTED CURBS AND BE MARKED WITH |
| FREESTANDING SIGNS READING, "FIRE LANE - NO PARKING BY |
| ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL BE 12" X 18" |
| WITH A WHITE BACKGROUND AND RED LETTERS AND SHALL BE A |
| MAXIMUM OF SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE |
| SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW |
| AND BE SPACED A MAXIMUM OF 60 FEET APART. FLORIDA FIRE |
| PREVENTION CODE SECTION 18.2.3.5.3. |
| |
| WESLEY JOLIN |
| FIRE INVESTIGATOR & INSPECTOR |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |
| |