Plan Review Notes For Permit 13040437 |
Permit Number |
13040437 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-04-23 11:32:29 | PLANS DENIED | | 1) LANDLORD'S PLAN AND MECHANICAL PLAN | | PERMIT # 13040438 DO NOT MATCH.LANDLORD PLAN | | SHOWS MAKE UP AIR AND EXHAUST GOING TO LANDLORD'S | | STORAGE. FIRE DAMPERS ARE REQUIRED AT THE MAKE UP AIR | | AND EXHAUST WALL PENETRATION. | | PER SECTION 607.5.2 FIRE BARRIERS. | | LANDLORD'S PLAN SHOW FIRE DAMPERS AS NEW, | | MECHANICAL PLAN SHOWS FIRE DAMPERS AS EXISTING. | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | |
|