2013-04-23 11:32:29PLANS DENIED
 1) LANDLORD'S PLAN AND MECHANICAL PLAN
 PERMIT # 13040438 DO NOT MATCH.LANDLORD PLAN
 SHOWS MAKE UP AIR AND EXHAUST GOING TO LANDLORD'S
 STORAGE. FIRE DAMPERS ARE REQUIRED AT THE MAKE UP AIR
 AND EXHAUST WALL PENETRATION.
 PER SECTION 607.5.2 FIRE BARRIERS.
 LANDLORD'S PLAN SHOW FIRE DAMPERS AS NEW,
 MECHANICAL PLAN SHOWS FIRE DAMPERS AS EXISTING.