 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION AND SHEET A-1 INDICATE THE
 PROJECT ADDRESS AS 701 SOUTH ROSEMARY AVENUE; HOWEVER,
 THE MEP SHEETS INDICATE AN ADDRESS OF 700 SOUTH
 ROSEMARY AVENUE. PLEASE COORDINATE THE CORRECT ADDRESS.
  
 SHEET M-1: NO FIRE DAMPER PROVIDED IN DUCTWORK
 PENETRATING LANDLORD STORAGE ROOM #102.
  
 GENERAL: EACH FIRE BARRIER SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: LANDLORD STORAGE #102 DOES NOT INDICATE ANY OF
 THE FOLLOWING INFORMATION: COMMODITY CLASS OF
 COMBUSTIBLES (PER NFPA 13), QUANTITY, STORAGE
 ARRANGEMENT (RACKS, PILE, BIN, ETC.), STORAGE HEIGHT,
 AISLE LAYOUT, ETC.
  
 GENERAL: PROVIDE PORTABLE FIRE EXTINGUISHERS.
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT
 EXCEED 75 FEET.
  
 GENERAL: FOR ISSUANCE OF A GENERAL BUILDING PERMIT,
 SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE
 REQUIRES SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS
 FOR THE DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC
 FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 GENERAL: NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED.
 PER FBC SECTION 907.1.1 CONSTRUCTION DOCUMENTS -
 "CONSTRUCTION DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE, THE
 FLORIDA FIRE PREVENTION CODE, AND RELEVANT LAWS,
 ORDINANCES, RULES AND REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL."
  