Plan Review Notes
Plan Review Notes For Permit 13040435
Permit Number 13040435
Review Stop B
Sequence Number 1
Notes
Date Text
2013-04-12 15:17:242010 FBC
  
 DENIED BY BUILDING
  
 1) THE SBS MODIFIED ROOF SYSTEM ON PAGE 31 OF PRODUCT
 APPROVAL NOA NO.08-0410.09 HAS A MAXIMUM DESIGN
 PRESSURE OF -45 PSF AND LIMITATION #9 WHICH DOES NOT
 ALLOW ENHANCED FASTENING TO INCREASE THE DESIGN
 PRESSURE. THIS PRESSURE IS TOO LOW FOR THE PERIMETER
 AND CORNER AREAS FOR A FLAT ROOF ON A STRUCTURE LOCATED
 IN EXPOSURE CATEGORY C WITH A 170 MPH ULTIMATE / 132
 NOMINAL WIND SPEED. PLEASE SELECT A SYSTEM WITH
 ADEQUATE DESIGN PRESSURES OR ONE THAT ALLOWS ENHANCED
 FASTENING. NOTE: RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING ARE REQUIRED TO BE SIGNED AND SEALED BY A
 FLORIDA LICENSED DESIGN PROFESSIONAL PER LIMITATION #7
 OF THIS NOA. DCA RULE 9N-3 AND FBCR301.2.1
  
 2) TWO COPIES OF PRODUCT APPROVALS AND CALCULATIONS ARE
 REQUIRED TO BE SUBMITTED FOR PERMIT. CITY AMENDMENTS
 107.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]