2013-04-16 12:36:11 | PROVISO PASS - PROCEED AT OWN RISK | | | | 1) THE GENERATOR BUILDING DOES NOT MATCH THE APPROVED | | SITE PLAN ELEVATIONS - SPECIFICALLY THE APPROVED | | ELEVATIONS OF THE GENERATOR BUILDING DID NOT INCLUDE | | GRILLS FOR THE VENTS FACING MILITARY TRAIL. THE WALL | | AND LANDSCAPE DO NOT PROVIDE ADEQUATE BUFFER FOR THE | | PROPOSED ELEVATION. | | | | 2) ZONING DID NOT APPROVE THE GENERATOR BUILDING | | ELEVATIONS WITH THE MASTER BUILDING PERMIT. | | | | 3) ZONING APPROVES THE SPECIFIC PERMIT REVISION TO | | RAISE THE TIE BEAM WITH THE PROVISO THAT THE DESIGN | | TEAM MEETS WITH STAFF TO DETERMINE HOW THE WEST | | ELEVATION OF THE GENERATOR BUILDING WILL BE REVISED OR | | PROPERLY SCREENED. | | | | 4) THE FINAL ELEVATIONS OF THE GENERATOR SHALL BE | | SUBMITTED AS A PERMIT REVISION PRIOR TO THE CERTIFICATE | | OF COMPLETION FOR THE GENERATOR BUILDING AND ANY OTHER | | PLAN REVISIONS TO VERIFY SCREENING SHALL ALSO BE | | SUBMITTED. | | | | PROCEED AT OWN RISK | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|