Plan Review Notes
Plan Review Notes For Permit 13040365
Permit Number 13040365
Review Stop E
Sequence Number 1
Notes
Date Text
2013-04-16 07:20:06HOLD ON PLANS INDICATES 4X FEE ON PERMITS
  
 PERMIT INDICATES THIS IS A PRIMARY PERMIT, NO FLOOR
 PLAN, EQUIPMENT OR OTHER PERMITS ARE ATTACHED
  
 PROVIDE ALL LOADS AND LOAD CALCULATIONS FOR THIS
 SERVICE OR IDENTIFY AS "CONSTRUCTION AND SECURITY
 TEMPORARY" WITH NO OCCUPANCY PERMITTED
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 ELECTRICAL SERVICE AND SWITCH GEAR. NEC 110.9, 110.10
  
 OVERCURRENT TO BE INTEGRAL TO SERVICE DISCONNECT OR
 IMMEDIATELY ADJACENT, NOT THROUGH A WALL 230.91
  
 PROVIDE PROPER DOWNSTREAM RATINGS OF EQUIPMENT IN
 ACCORDANCE WITH THE FAULT CURRENT AND/OR PROVIDE PROPER
 SERIES RATINGS VALUES 240.4 (B) (C) (F), 240.12
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 PROVIDE AND ILLUSTRATE THE SAFE WORKING CLEARANCES AND
 DEDICATED WORKING SPACE AT ALL ELECTRICAL PANEL BOARDS
 AND TRANSFORMERS. NEC 110.26, 240.24
  
 GROUNDING ELECTRODE CONDUCTOR APPEARS TO BE IMPROPERLY
 SIZED FOR BONDING OF ALL SYSTEMS AND PROVIDE BONDING OF
 ALL SYSTEMS AND BUILDING STEEL, AS APPLICABLE 250.66,
 250.104
  