2013-04-16 07:20:06 | HOLD ON PLANS INDICATES 4X FEE ON PERMITS |
| |
| PERMIT INDICATES THIS IS A PRIMARY PERMIT, NO FLOOR |
| PLAN, EQUIPMENT OR OTHER PERMITS ARE ATTACHED |
| |
| PROVIDE ALL LOADS AND LOAD CALCULATIONS FOR THIS |
| SERVICE OR IDENTIFY AS "CONSTRUCTION AND SECURITY |
| TEMPORARY" WITH NO OCCUPANCY PERMITTED |
| |
| INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE |
| ELECTRICAL SERVICE AND SWITCH GEAR. NEC 110.9, 110.10 |
| |
| OVERCURRENT TO BE INTEGRAL TO SERVICE DISCONNECT OR |
| IMMEDIATELY ADJACENT, NOT THROUGH A WALL 230.91 |
| |
| PROVIDE PROPER DOWNSTREAM RATINGS OF EQUIPMENT IN |
| ACCORDANCE WITH THE FAULT CURRENT AND/OR PROVIDE PROPER |
| SERIES RATINGS VALUES 240.4 (B) (C) (F), 240.12 |
| |
| AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN |
| SERVICE GROUND. NEC 250.94 |
| |
| PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. |
| NEC 110.22, 110.16, 110.22 |
| |
| PROVIDE AND ILLUSTRATE THE SAFE WORKING CLEARANCES AND |
| DEDICATED WORKING SPACE AT ALL ELECTRICAL PANEL BOARDS |
| AND TRANSFORMERS. NEC 110.26, 240.24 |
| |
| GROUNDING ELECTRODE CONDUCTOR APPEARS TO BE IMPROPERLY |
| SIZED FOR BONDING OF ALL SYSTEMS AND PROVIDE BONDING OF |
| ALL SYSTEMS AND BUILDING STEEL, AS APPLICABLE 250.66, |
| 250.104 |
| |