Plan Review Notes
Plan Review Notes For Permit 13040308
Permit Number 13040308
Review Stop P
Sequence Number 1
Notes
Date Text
2013-04-18 09:39:09 
 FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET PD2.00 A HOLE IS REQUIRED IN THE BOTTOM OF THE
 ABANDONED GREASE TRAP PER HEALTH DEPT.
  
 2. SHEET A6.03 THE ACCESSAIBLE SHOWER STALLS DO NOT
 MEET UFAS FIGURE 35(A) OR FBC ACCESSIBILITY FIGURE
 608.2.1 FOR CLEAR SPACE.
 CLEARANCE OF 36 INCHES (915 MM) WIDE MINIMUM BY 48
 INCHES (1220 MM) LONG MINIMUM MEASURED FROM THE CONTROL
 WALL SHALL BE PROVIDED.
  
 3. SHEET A6.05 DETAIL 10 PLEASE SUBMIT THE APPROVALS
 FOR THE LIQUID APPLIED WATERPROOFING.
 P-417.5.2.5 SHEET-APPLIED, LOAD-BEARING, BONDED,
 WATERPROOF MEMBRANES. SHEET-APPLIED, LOAD-BEARING,
 BONDED, WATERPROOF MEMBRANES SHALL MEET REQUIREMENTS OF
 ANSI A118.10 AND SHALL BE APPLIED IN ACCORDANCE WITH
 THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676