Plan Review Notes For Permit 13040308 |
Permit Number |
13040308 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-04-18 09:39:09 | | | FBC 2010 EXISTING BUILDING CODE | | FBC 2010 ACCESSIBILITY CODE | | FBC 2010 PLUMBING REVIEW #1 | | DENIED: | | | | 1. SHEET PD2.00 A HOLE IS REQUIRED IN THE BOTTOM OF THE | | ABANDONED GREASE TRAP PER HEALTH DEPT. | | | | 2. SHEET A6.03 THE ACCESSAIBLE SHOWER STALLS DO NOT | | MEET UFAS FIGURE 35(A) OR FBC ACCESSIBILITY FIGURE | | 608.2.1 FOR CLEAR SPACE. | | CLEARANCE OF 36 INCHES (915 MM) WIDE MINIMUM BY 48 | | INCHES (1220 MM) LONG MINIMUM MEASURED FROM THE CONTROL | | WALL SHALL BE PROVIDED. | | | | 3. SHEET A6.05 DETAIL 10 PLEASE SUBMIT THE APPROVALS | | FOR THE LIQUID APPLIED WATERPROOFING. | | P-417.5.2.5 SHEET-APPLIED, LOAD-BEARING, BONDED, | | WATERPROOF MEMBRANES. SHEET-APPLIED, LOAD-BEARING, | | BONDED, WATERPROOF MEMBRANES SHALL MEET REQUIREMENTS OF | | ANSI A118.10 AND SHALL BE APPLIED IN ACCORDANCE WITH | | THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. | | | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 |
|