Plan Review Notes For Permit 13040308 |
Permit Number |
13040308 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-04-18 15:09:50 | PLANS DENIED | | 1) NEW MECHANICAL ROOM # 129 IS MISSING FIRE DAMPERS | | INTO ROOMS 127 AND 128. | | PER SECTION 607.5.1 FIRE WALLS 2010 FBC (M) | | 2) REFER TO SECTION 501.2.1 LOCATION OF EXHAUST | | OUTLETS. | | 2010 FBC (M) | | 3) REFER TO SECTION 501.2.2 EXHAUST OPENING PROTECTION. | | 2010 FBC (M) | | 4) PROVIDE ALL DUCT SIZE ON AIR HANDLER # 5 ON THE | | PLANS | | 5) PROVIDE A DETAIL ON THE PLANS FROM THE ENGINEER ON | | HOW THE | | DEHUMIDIFIER STAND IS MOUNTED TO THE WALL.PER SECTION | | 301.12 | | WIND RESISTANCE | | 6) PROVIDE A DETAIL FROM THE ENGINEER ON HOW THE | | EXHAUST FAN | | CURB IS TIED DOWN TO THE ROOF AND EXHAUST FAN IS TIED | | TO THE CURB . | | PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M) | | 7) PLEASE CLARIFY THE BATHROOM EXHAUST ON THE PLANS | | PER SECTION 107 FBC 2010 | | 8) KITCHEN HOOD REQUIRE SEPARATE APPLICATION PLANS AND | | PERMIT. | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | |
|