Plan Review Notes
Plan Review Notes For Permit 13040308
Permit Number 13040308
Review Stop M
Sequence Number 1
Notes
Date Text
2013-04-18 15:09:50PLANS DENIED
 1) NEW MECHANICAL ROOM # 129 IS MISSING FIRE DAMPERS
 INTO ROOMS 127 AND 128.
 PER SECTION 607.5.1 FIRE WALLS 2010 FBC (M)
 2) REFER TO SECTION 501.2.1 LOCATION OF EXHAUST
 OUTLETS.
 2010 FBC (M)
 3) REFER TO SECTION 501.2.2 EXHAUST OPENING PROTECTION.
 2010 FBC (M)
 4) PROVIDE ALL DUCT SIZE ON AIR HANDLER # 5 ON THE
 PLANS
 5) PROVIDE A DETAIL ON THE PLANS FROM THE ENGINEER ON
 HOW THE
 DEHUMIDIFIER STAND IS MOUNTED TO THE WALL.PER SECTION
 301.12
 WIND RESISTANCE
 6) PROVIDE A DETAIL FROM THE ENGINEER ON HOW THE
 EXHAUST FAN
 CURB IS TIED DOWN TO THE ROOF AND EXHAUST FAN IS TIED
 TO THE CURB .
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 7) PLEASE CLARIFY THE BATHROOM EXHAUST ON THE PLANS
 PER SECTION 107 FBC 2010
 8) KITCHEN HOOD REQUIRE SEPARATE APPLICATION PLANS AND
 PERMIT.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  