2013-06-07 09:40:026/7/13 UPDATE
 U/G GAS IS P.E. SHOWN ON P 3.00 OK
2013-04-18 09:35:55FBC 2010 FUEL GAS REVIEW #1
 ***PROVISO***
  
 SHEET P3.00 THE GAS DIAGRAM LISTS THE MATERIAL AS
 SCHEDULE 40 METALIC PIPE. THE RUN FROM THE PROPANE TANK
 APPEARS TO BE UNDERGROUND. 404.9 PROTECTION AGAINST
 CORROSION. ZINC COATINGS (GALVANIZING) SHALL NOT BE
 DEEMED ADEQUATE PROTECTION FOR GAS PIPING UNDERGROUND.
 404.9.2 PROTECTIVE COATINGS AND WRAPPING.
 PIPE PROTECTIVE COATINGS AND WRAPPINGS SHALL BE
 APPROVED FOR THE APPLICATION AND SHALL BE FACTORY
 APPLIED.
  