Plan Review Notes For Permit 13040308 |
Permit Number |
13040308 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-06-07 09:40:02 | 6/7/13 UPDATE | | U/G GAS IS P.E. SHOWN ON P 3.00 OK | 2013-04-18 09:35:55 | FBC 2010 FUEL GAS REVIEW #1 | | ***PROVISO*** | | | | SHEET P3.00 THE GAS DIAGRAM LISTS THE MATERIAL AS | | SCHEDULE 40 METALIC PIPE. THE RUN FROM THE PROPANE TANK | | APPEARS TO BE UNDERGROUND. 404.9 PROTECTION AGAINST | | CORROSION. ZINC COATINGS (GALVANIZING) SHALL NOT BE | | DEEMED ADEQUATE PROTECTION FOR GAS PIPING UNDERGROUND. | | 404.9.2 PROTECTIVE COATINGS AND WRAPPING. | | PIPE PROTECTIVE COATINGS AND WRAPPINGS SHALL BE | | APPROVED FOR THE APPLICATION AND SHALL BE FACTORY | | APPLIED. | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|