2013-04-23 13:03:55BUILDING PLAN REVIEW
 PERMIT: 13040308
 ADD: 2901 TUXEDO AVENUE
 CONT: WEST CONSTRUCTION
 TEL: (561)588-2027
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1 ST REVIEW
 DATE: APRIL 23/ 2013
 ACTION: DENIED
  
 1) SHEET A1.00:
 1A ) UNDER THE HEADING OF SITE CODE COMPLIANCE THE
 PLANS INDICATE 13 NEW PARKING SPACES BUT THERE IS A
 TOTAL OF 85 PARKING SPACES THAT WILL REQUIRE 4
 ACCESSIBLE PARKING SPACES SEE THE 2010 FL ACCESSIBILITY
 CODE TABLE 208.2.
  
 1B) THE PLANS ALSO SHOW THE 2 ACCESSIBLE PARKING SPACES
 GROUPED TOGETHER. THE 2010 FL ACCESSIBILITY CODE
 SECTION 208.3.1 WHEN PARKING SERVES MORE THAN ONE
 ACCESSIBLE ENTRANCE, PARKING SPACES COMPLYING WITH 502
 SHALL BE DISPERSED AND ON THE SHORTEST ACCESSIBLE ROUTE
 TO THE ACCESSIBLE ENTRANCE.
  
 1C) THE NEW PARKING SPACES SHOWN TO THE NORTH OF THE
 BUILDING ARE DOUBLE STRIPED TO THE CITY ZONING STANDARD
 BUT THE PARKING TO THE WEST OF THE BUILDING ARE SINGLE
 STRIPED AND ARE BEING RE-STRIPED. THEY WILL NEED TO BE
 DOUBLE STRIPED TO MEET THE CITY ZONING STANDARDS.
  
 1D) JUST A NOTE OF CAUTION ON THE REDESIGN, 2010 FL
 ACCESSIBILITY CODE 208.3.1 ALL SPACES MUST BE LOCATED
 ON AN ACCESSIBLE ROUTE THAT IS 44 INCHES WIDE AND SO
 THAT USERS ARE NOT COMPELLED TO WALK OR WHEEL BEHIND
 VEHICLES EXCEPT BEHIND HIS OR HER OWN VEHICLE.
  
 1E) THIS BUILDING IS LOCATED IN A FLOOD ZONE, A-9 AND
 WILL NEED FLOOD ZONE CERTIFICATES:
 1) BEFORE THE ISSUANCE OF THE PERMIT WITH PROPOSED
 ELEVATION OF FINISHED SLAB IN
 NGVD.
 2) ONCE THE FLOOR SLAB HAS BEEN POURED AND FINISHED.
 3) BEFORE THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY,
 OR CERTIFICATE OF
 COMPLETION.
 FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31,2015
  
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE
 FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING
 COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS
 CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED
 ON THE NEW FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 2) SHEET LS1.01:
 2A) NEW SUPPLY AND STORAGE ROOM # 116 AND OFFICE # 114,
 MISSING OCCUPANCY SEPARATION BETWEEN THESE OCCUPANCIES.
 THIS STORAGE AREA IS LARGER THAN 10 % OF THE BUILDING
 FOOTPRINT NO LONGER BEING CLASSIFIED AS A ACCESSORY
 OCCUPANCY. FBC-B 508.2.1.
  
 2B) THE NEW MECHANICAL ROOM # 129 AND STORAGE ROOMS TO
 THE EAST ARE MISSING THE OCCUPANCY SEPARATION WALL
 CLASSIFICATION WITH THE ASSEMBLY OCCUPANCY, FBC-B TABLE
 508.4.
  
 2C) THE NEW MECHANICAL ROOM # 123 INDICATES 2 OF THE
 WALLS WITH A OCCUPANCY SEPARATION RATING BUT MISSING
 THE OTHER 2 WALLS, FBC-B TABLE 508.2.5.
  
 2D) SHEET A.101 WALL TAGS IDENTIFYING WALL TYPE DO NOT
 INDICATE RATED WALL OCCUPANCY SEPARATION AS SHOWN ON
 THE LS PLAN. WALLS TYPES LOCATED ON SHEET A5.01 DOORS
 ON A7.01.
  
 3) SHEET A5.02
 3A) DETAIL # 5 NEW RAMP, PLEASE SEE HANDRAIL HEIGHT AT
 STAIR, 2010 FL ACCESSIBILITY CODE 505.4 HANDRAIL HEIGHT
 BETWEEN 34?-38?.
  
 3B) DETAIL # 5 ALSO IS MISSING THE HANDRAIL EXTENSIONS
 REQUIRED BY FL ACCESSIBILITY CODE 505.10.
  
 3C) DETAIL #9 THE WALL MOUNTED DETAIL INDICATES THE
 MINIMUM DISTANCE FROM THE WALL IS 2 ? INCHES PLEASE
 REVIEW 2010 FL ACCESSIBILITY CODE 505.5 CLEARANCE.
  
 3D) DETAIL # 6 & 8 THE BOTTOM LANDING IS NOT
 DIMENSIONED BUT SCALES OUT LESS THAN 5?-0? IN LENGTH (
 DIRECTION OF TRAVEL) SEE FL ACCESSIBILITY CODE 405.7.3.
  
 4A) SHEET A4.01, A4.02 & A5.04 BRICK WALL DETAILS 1 &
 2, PLEASE REVIEW 2010 FBC-B SECTION 2114.2 CONCRETE
 BEARING LEDGE. BRICK, STONE OR OTHER VENEER SHALL BE
 SUPPORTED BY A CONCRETE BEARING LEDGE AT LEAST EQUAL TO
 THE TOTAL THICKNESS OF THE BRICK, STONE OR OTHER
 VENEER, WHICH IS POURED INTEGRALLY WITH THE CONCRETE
 FOUNDATION. NO SUPPLEMENTAL CONCRETE FOUNDATION POURS
 WHICH WILL CREATE A HIDDEN COLD JOINT SHALL BE USED
 WITHOUT SUPPLEMENTAL TREATMENT IN THE FOUNDATION UNLESS
 THERE IS AN APPROVED PHYSICAL BARRIER. AN APPROVED
 PHYSICAL BARRIER SHALL ALSO BE INSTALLED FROM BELOW THE
 WALL SILL PLATE OR FIRST BLOCK COURSE HORIZONTALLY TO
 EMBED IN A MORTAR JOINT. IF MASONRY VENEER EXTENDS
 BELOW GRADE, A TERMITE PROTECTIVE TREATMENT MUST BE
 APPLIED TO THE CAVITY CREATED BETWEEN THE VENEER AND
 THE FOUNDATION, IN LIEU OF A PHYSICAL BARRIER.
  
 EXCEPTION: VENEER SUPPORTED BY A SHELF, ANGLE OR LINTEL
 SECURED TO THE FOUNDATION SIDEWALL IN ACCORDANCE WITH
 TMS 402/ACI 530/ASCE 5, PROVIDED AT LEAST A 6-INCH (152
 MM) CLEAR INSPECTION SPACE OF THE FOUNDATION SIDEWALL
 EXTERIOR EXISTS BETWEEN THE VENEER AND THE TOP OF ANY
 SOIL, SOD, MULCH OR OTHER ORGANIC LANDSCAPING
 COMPONENT, DECK, APRON, PORCH, WALK OR ANY OTHER WORK
 IMMEDIATELY ADJACENT TO OR ADJOINING THE STRUCTURE.
  
 4B) PLANS DO NOT INDICATE HOW THE BRICK VENEER WILL BE
 ATTACHED TO THE CMU WALL, PROVIDE COMPLIANCE WITH 2010
 FBC-B 1405.6 ANCHORED MASONRY VENEER.
  
 5) COMPLIED SEE SHEET G0.01 FOR APPROVAL OF COMPONENTS
 & CLADDING PRODUCT APPROVALS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
2013-04-17 16:08:25 
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved