2013-04-19 15:02:34VOLTAGE DROP CALCULATION DOES NOT SEEM TO MATCH
 REQUIRED VOLTAGE RATING AND PROPOSED EQUUIPMENT. IS
 ANNUNCIATION PHASED, 2 ABOVE AND ONE BELOW FLOOR OF
 INITIATION?
 ADDED MECHANICAL STOP FOR DUCT DETECTORS
 DOES NOT APPEAR PULL STATIONS ARE LOCATED AT EACH POINT
 OF NATURAL ESCAPE? RECREATION ROOM, MAINTENANCE ROOM
 CALLED ENGINEER REGARDING VD. HE DID NOT HAVE THE
 DRAWINGS AT THIS TIME. WILL REVIEW AND CALL ME BACK
 SPOKE WITH DESIGN ENGINEER. CALCULATIONS AND VOLTAGES
 APPEAR OK BASED ON CONVERSATION AND EXPECTED VOLTAGES
 OF EQUIPMENT TO BE VERIFIED IN THE FIELD. BATTERY POWER
 APPEARS TO BE SUFFICIENT BASED ON DRAW OF PROPOSED
 DEVICES. SPOKE TO WESLEY ON PULL STATIONS AND THIS
 SEEMS TO BE OK AS IT IS A SPRINKLERED BUILDING.
  