| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| *****APPROVED W/ PROVISIONS - SUBMIT REVISION***** |
| |
| SHEET G101: EXIT DOOR #106 (LOCATED IN DAY ROOM 4 - |
| #106) APPEARS TO BE EQUIPPED WITH A MAGNETIC LOCK AND |
| CARD READER. PER SECTION 7.2.1.6.2 OF NFPA 101 FLORIDA |
| EDITION 2009 ALLOWS ACCESS CONTROLLED EGRESS DOORS |
| PROVIDED THAT ALL SEVEN OF THE FOLLOWING CRITERIA ARE |
| MET: |
| 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE, |
| ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT |
| ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON |
| DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER |
| TO THE SENSOR. |
| 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL |
| SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK |
| THE DOORS IN THE DIRECTION OF EGRESS. |
| 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE |
| DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE |
| LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND |
| WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS. |
| 4. THE MANUAL RELEASE DEVICE SHALL BE READILY |
| ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS |
| PUSH TO EXIT. |
| 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL |
| RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK, |
| INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS, |
| AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN |
| 30 SECONDS. |
| 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL |
| AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF |
| EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE |
| FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET. |
| 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER |
| SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL |
| AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF |
| EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE |
| FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET. |
| |
| SHEET E301: THREE EXIT SIGNS MISSING FROM PLAN. REFER |
| TO SHEET G101 FOR COORDINATION. |
| |
| SHEET E401: FLOOR PLAN IS NOT THE SAME AS THE |
| ARCHITECTURAL FLOOR PLAN OF SHEET A101. |
| |
| SHEET E401: NO FIRE ALARM NOTIFICATION APPLIANCES |
| LOCATED IN DAY ROOM 3 & 4 OR IN IDT #109. FIRE ALARM |
| ANNUNCIATOR PANEL MISSING FROM RECEPTION #102. |
| |