2013-04-16 16:07:55BUILDING PLAN REVIEW
 PERMIT: 13040187
 ADD: 400 N FLAGLER # 1701
 CONT: A. D. SABA ENTERPRISES
 TEL: (561)969-2920
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1A) GENERAL NOTE # 12 STATES FBC-B 1207.3 WHICH DEALS
 WITH STRUCTURE BORNE SOUND, 1207.3 STRUCTURE-BORNE
 SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 IF FLOORING IS TO BE REPLACED WITH TILE OR MARBLE TYPE
 PRODUCTS THEN A REVISION WILL BE REQUIRED MEETING THESE
 REQUIREMENTS.
  
 1B) IF FLOORING IS BEING REPLACED WITH A TILE OR
 SIMILAR PRODUCT THEN THE FLOOR INSULATION WILL ALSO
 NEED TO MEET 2010 FBC-B 603.1(2) EXCEPTION (1).
 INSULATION PLACED BETWEEN TWO LAYERS OF NONCOMBUSTIBLE
 MATERIALS WITHOUT AN INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 100.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved