2013-04-16 16:07:55 | BUILDING PLAN REVIEW |
| PERMIT: 13040187 |
| ADD: 400 N FLAGLER # 1701 |
| CONT: A. D. SABA ENTERPRISES |
| TEL: (561)969-2920 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1A) GENERAL NOTE # 12 STATES FBC-B 1207.3 WHICH DEALS |
| WITH STRUCTURE BORNE SOUND, 1207.3 STRUCTURE-BORNE |
| SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| IF FLOORING IS TO BE REPLACED WITH TILE OR MARBLE TYPE |
| PRODUCTS THEN A REVISION WILL BE REQUIRED MEETING THESE |
| REQUIREMENTS. |
| |
| 1B) IF FLOORING IS BEING REPLACED WITH A TILE OR |
| SIMILAR PRODUCT THEN THE FLOOR INSULATION WILL ALSO |
| NEED TO MEET 2010 FBC-B 603.1(2) EXCEPTION (1). |
| INSULATION PLACED BETWEEN TWO LAYERS OF NONCOMBUSTIBLE |
| MATERIALS WITHOUT AN INTERVENING AIRSPACE SHALL BE |
| ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| 100. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |