Plan Review Notes For Permit 13040093 |
Permit Number |
13040093 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-04-23 17:07:22 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 2ND REVIEW - SOUND TRANSMISSION TEST REPORTS WERE | | SUBMITTED. COMMENTS FROM FIRST REVIEW (SEE BELOW) ARE | | REGARDING FLAME SPREAD. | | | | 1. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM | | E 84 OR UL 723. | | | | IF THE DOC-FF-1-70 (TEST REFERRED TO ON THE DOCUMENT | | SUBMITTED) WOULD LIKE TO BE PRESENTED AS ALTERNATIVE | | MATERIALS AND METHODS, SUBMIT A COPY OF THE ACTUAL TEST | | REPORT WITH AN ANALYSIS OF HOW THIS TEST MEETS OR | | EXCEEDS THE REQUIREMENTS OF ASTM E 84 OR UL 723. | | | | |
|