Plan Review Notes
Plan Review Notes For Permit 13040093
Permit Number 13040093
Review Stop B
Sequence Number 1
Notes
Date Text
2013-04-08 13:44:54****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 IF THE DOC-FF-1-70 (TEST REFERRED TO ON THE DOCUMENT
 SUBMITTED) WOULD LIKE TO BE PRESENTED AS ALTERNATIVE
 MATERIALS AND METHODS, SUBMIT A COPY OF THE ACTUAL TEST
 REPORT WITH AN ANALYSIS OF HOW THIS TEST MEETS OR
 EXCEEDS THE REQUIREMENTS OF ASTM E 84 OR UL 723.
  
  