Plan Review Notes For Permit 13040088 |
Permit Number |
13040088 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-04-03 10:23:36 | FBC 2010 PLUMBING REVIEW #1 | | DENIED: | | | | NOT ENOUGH INFORMATION FOR REVIEW. PLEASE SUBMIT | | THEFOLLOWING: | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | FBC?2010 FUEL GAS. | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. | | 3. TYPE OF GAS, (LP OR NATURAL). | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | THE SYSTEM. REFER TO THE FBC?2007 FUEL GAS SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | AND/OR SYSTEM PER THE FBC?2010 FUEL GAS APPENDIX A ? | | USE OF CAPACITY SECTION A.3.1(4) | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC?2007 | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | PSI. | | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | TERMINATION OF THE GAS VENTS PER FBC?2010 FUEL GAS CODE | | SEC. 502 THRU 505. | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805?6692 | | EMAIL [email protected] | | FAX # 805?6676 | | |
|