Plan Review Notes
Plan Review Notes For Permit 13040088
Permit Number 13040088
Review Stop G
Sequence Number 1
Notes
Date Text
2013-04-03 10:23:36FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 NOT ENOUGH INFORMATION FOR REVIEW. PLEASE SUBMIT
 THEFOLLOWING:
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC?2010 FUEL GAS.
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL).
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC?2007 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC?2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC?2007
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC?2010 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805?6692
 EMAIL [email protected]
 FAX # 805?6676
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved