2013-04-12 11:57:23 | BUILDING PLAN REVIEW |
| PERMIT: 113040039 |
| ADD: 13040039 |
| CONT: ROBB CONSTRUCTION |
| TEL: (561)346-9509 |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: 4/12/2013 |
| ACTION: DENIED |
| |
| 1) THE VALUE ON THE PERMIT IS LISTED AS $2,400 DOLLARS, |
| THIS WOULD NOT EVEN COVER THE COST FOR THE INTERIOR |
| DEMOLITION SHOWN ON D 1.1. |
| W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| APPLICABLE GOVERNING AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2) PLEASE SHOW THE FURNATURE LAYOUT ON THE LS PLAN, IT |
| IS UNCLEAR AS TO THE USAGE OF THIS SPACE. PLEASE ALSO |
| NOTE MISSING EMERGENCY LIGHTS IN THE CORRIDOR ADJACENT |
| TO THE SERVER ROOM, 2010 FBC-B 1006.1.2. |
| |
| 3) MISSING THE EXIT DIRECTIONAL LIGHT THAT LEADS INTO |
| THE CORRIDOR FROM THE SUPERVISORY AREA. 1006.3.1 EXIT |
| SIGNS. |
| |
| 4) MISSING THE QUALIFIERS SIGNATURE ON THE PERMIT |
| APPLICATION, A HOLD IS ON THE PERMIT TO NOT ISSUE UNTIL |
| WE RECEIVE THE QUALIFIERS SIGNATURE. |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |