2013-07-31 15:01:05 | RESIDENTIAL (R3) ADDITION, RE-SUBMITTAL MECHANICAL | | REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | | | 1- PERSON RESPONSIBLE FOR THE DESIGN OF THE A/C PLAN | | NEEDS TO PROVIDE HIS NAME AND SIGNATURE AS REQUIRED BY | | SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | 2- DRAWINGS SUBMITTED HAVE A COPYRIGHT NOTE AT THE | | BOTTOM OF THE PAGE FROM AN ARCHITECT. ARCHITECT'S PLANS | | NEED TO BE SIGNED AND SEALED AS REQUIRED BY CHAPTER 481 | | FLORIDA STATUTE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|