Plan Review Notes
Plan Review Notes For Permit 13030854
Permit Number 13030854
Review Stop P
Sequence Number 1
Notes
Date Text
2013-04-08 16:57:40RESIDENTIAL (R3) ADDITION PLUMBING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PLUMBING RISER DIAGRAM DOESN'T MATCH PLANS. FLOOR
 PLAN DOESN'T SHOW ANY WASHER MACHINE.
  
 2- REVISE PLUMBING RISER DIAGRAM. ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUP SHALL CONNECT TO THE
 WET-VENTED HORIZONTAL BRANCH DRAIN. REVISE PLUMBING
 RISER DIAGRAM AS REQUIRED. SEC. P3108.1 OF 2010
 FBC-RESIDENTIAL.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712