Plan Review Notes For Permit 13030854 |
Permit Number |
13030854 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-04-09 11:44:35 | RESIDENTIAL (R3) ADDITION MECHANICAL REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- INFORMATION SHOWN ON ENERGY CALCULATIONS AND | | RESIDENTIAL EQUIPMENT CALCULATIONS DON'T MATCH. CHECK | | THE TOTAL COOLING AND HEATING LOADS. SEC. 107.2.1 CITY | | AMENDMENTS TO FBC. | | | | 2- EQUIPMENT SIZING CALCULATIONS TAKES INTO | | CONSIDERATION A KITCHEN. ACCORDING TO ARCHITECT'S PLANS | | SUBMITTED THERE IS NOT KITCHEN. REVISE AS REQUIRED. | | SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | 3- CFM'S SHOWN ON THE EQUIPMENT SIZING CALCULATIONS | | DON'T MATCH A/C PLAN. REVISE AS REQUIRED. SEC. 107.2.1 | | CITY AMENDMENTS. | | | | 4- EQUIPMENT MODELS SHOWN ON THE CERTIFICATE OF PRODUCT | | RATINGS DON'T MATCH EQUIPMENT SHOWN ON THE A/C PLAN. | | REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. | | | | 5- A/C PLAN NEEDS TO BE SIGNED AND SEALED BY THE | | ARCHITECT SHOWN ON THE TITLE BLOCK. SEC. 107.1 CITY | | AMENDMENTS. | | | | 6- WHERE IS THE NATURAL GAS FURNACE SHOWN ON THE LAST | | PAGE OF EQUIPMENT SIZING CALCULATIONS?. SEC. 107.2.1 | | CITY AMENDMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|