2013-04-09 11:44:35RESIDENTIAL (R3) ADDITION MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- INFORMATION SHOWN ON ENERGY CALCULATIONS AND
 RESIDENTIAL EQUIPMENT CALCULATIONS DON'T MATCH. CHECK
 THE TOTAL COOLING AND HEATING LOADS. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 2- EQUIPMENT SIZING CALCULATIONS TAKES INTO
 CONSIDERATION A KITCHEN. ACCORDING TO ARCHITECT'S PLANS
 SUBMITTED THERE IS NOT KITCHEN. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 3- CFM'S SHOWN ON THE EQUIPMENT SIZING CALCULATIONS
 DON'T MATCH A/C PLAN. REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 4- EQUIPMENT MODELS SHOWN ON THE CERTIFICATE OF PRODUCT
 RATINGS DON'T MATCH EQUIPMENT SHOWN ON THE A/C PLAN.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 5- A/C PLAN NEEDS TO BE SIGNED AND SEALED BY THE
 ARCHITECT SHOWN ON THE TITLE BLOCK. SEC. 107.1 CITY
 AMENDMENTS.
  
 6- WHERE IS THE NATURAL GAS FURNACE SHOWN ON THE LAST
 PAGE OF EQUIPMENT SIZING CALCULATIONS?. SEC. 107.2.1
 CITY AMENDMENTS.
  