 1004 BUNKER ROAD
 SFD ADDITION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 VERIFY THE EXISTING HOME ALSO HAS SMOKE DETECTORS AND
 CARBON MONOXIDE DETECTORS. REMODELING OF AN EXISTING
 STRUCTURE IS REQUIRED TO INCLUDE INTERCONNECTED SMOKE
 ALARMS BOTH WITHIN AND OUTSIDE EACH SLEEPING AREA. IF
 THE RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR
 A FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. 2010
 FBC R314, 315
  
 SHOW THE LOCATION OF THE ELECTRICAL SERVICE AND
 EXISTING PANEL WITH MAIN DISCONNECTS. SHOW THE EXISTING
 AND NEW FEEDERS. VERIFY THAT ALL SERVICE DISCONNECTS
 ARE GROUPED IN ONE LOCATION. NEC 215.5, 230.2
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER