2013-04-02 12:05:12 | | | 13030854 | | 1004 BUNKER ROAD | | SFD ADDITION | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | VERIFY THE EXISTING HOME ALSO HAS SMOKE DETECTORS AND | | CARBON MONOXIDE DETECTORS. REMODELING OF AN EXISTING | | STRUCTURE IS REQUIRED TO INCLUDE INTERCONNECTED SMOKE | | ALARMS BOTH WITHIN AND OUTSIDE EACH SLEEPING AREA. IF | | THE RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR | | A FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED | | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. 2010 | | FBC R314, 315 | | | | SHOW THE LOCATION OF THE ELECTRICAL SERVICE AND | | EXISTING PANEL WITH MAIN DISCONNECTS. SHOW THE EXISTING | | AND NEW FEEDERS. VERIFY THAT ALL SERVICE DISCONNECTS | | ARE GROUPED IN ONE LOCATION. NEC 215.5, 230.2 | | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | SERVICE GROUND. NEC 250.94 | | | | THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | CIRCUIT. NEC 210.11 (C) (3) | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|