2013-04-03 10:02:47 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2010 |
| FBC-RESIDENTIAL THIS BUILDING IS LOCATED ON EXPOSURE |
| "C" NOT 'B". REVISE THE STRUCTURAL NOTES AND ALL THE |
| DESIGN PRESSURES ON SHEET A-1 TO CORRESPOND TO EXPOSURE |
| "C". ALSO, REVISE THE DESIGN PRESSURES ON WINDOWS/DOORS |
| SCHEDULES ON SHEET A-5 AS WELL. |
| |
| 2- PROPER DESIGN OPERATION OF THE MECHANICAL AND |
| ELECTRICAL SYSTEM CAN NOT BE ACHIEVED IF THE PLANS, |
| MECHANICAL EQUIPMENT AND ELECTRICAL CALCULATIONS DON'T |
| MATCH. FOR EXAMPLE; PLANS SHOW DRESSING ROOM, AN AREA |
| THAT LOOKS LIKE A KITCHEN BUT THERE IS NO NAME, AND |
| STORAGE. MECHANICAL EQUIPMENT AND ELECTRICAL |
| CALCULATIONS DON'T CORRESPOND TO THE ROOMS AND USES |
| SPECIFIED ON PLANS. REVISE AS REQUIRED TO MATCH. SEC. |
| 104.12 CITY AMENDMENTS TO FBC. |
| |
| *** CLARIFY: A) WHY DESIGNING A "DRESSING ROOM" WITH |
| SOME MANY WINDOWS, SEPARATE ENTRY LEADING TO THE STREET |
| AND HAVING TV AND PHONE OUTLETS. B) ROOM WITH LAYOUT OF |
| A COMPLETE KITCHEN (SEE FLOOR PLANS AND INTERIOR |
| ELEVATIONS), C) STORAGE ROOMS ADJACENT TO THE "KITCHEN" |
| AREA AND WITH TV AND PHONE OUTLETS ALSO. |
| |
| 3- PROVIDE PARTIAL LAYOUT OF EXISTING SPACES ADJACENT |
| TO THE NEW DRESSING ROOM TO VERIFY THAT EGRESS AND |
| VENTILATION ARE NOT AFFECTED BY BLOCKING THE WALL WITH |
| THE NEW ADDITION. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| |
| 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR; |
| A) FLAT ROOF AS SPECIFIED ON PLANS/DETAILS. AND PROVIDE |
| RAS 117 CALCULATIONS FOR PERIMETER AND CORNER AREAS |
| NAIL ENHANCING. |
| ***NOTE: IF PRODUCT APPROVAL SUBMITTED REQUIRES SIGNED |
| AND SEALED RAS 117 CALCULATIONS, THEN PROVIDE SIGNED |
| AND SEALED CALCULATIONS. |
| |
| B) SHUTTERS FOR DOORS THAT HAVE NO IMPACT GLAZING (SEE |
| NOA 09-0608.16 SUBMITTED). AND, PROVIDE COMPLETE |
| SHUTTERS INSTALLATION SCHEDULE. |
| |
| C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| PLANS/DETAILS. ***NOTE: PROVIDE ONLY THE PRODUCT |
| APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| CONNECTOR. |
| |
| D) FIBERGLASS EXTERIOR DOOR. NOA 06-1215.03 SUBMITTED |
| IS EXPIRED. NEED CURRENT ONE. |
| |
| E) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC. |
| 107.3.4.1 CITY AMENDMENTS TO FBC. |
| |
| 6- REVISE THE ENERGY CALCULATIONS (NEED AN ACCURATELY |
| COMPLETED FORM AS REQUIRED BY SEC. 103.2.1.1.2 OF 2010 |
| FBC-ENERGY CONSERVATION): |
| A) REVISE ITEM #7. THE AREA AVERAGE OVERHANG DEPTH IS |
| NOT 3.00FT. SEE PLANS AND REVISE AS REQUIRED. |
| |
| B) REVISE/CLARIFY IF INSTALLING NEW KITCHEN. REVISE |
| "SPACES" SECTION ON SHEET 2 OF 5. SEE PLANS. |
| |
| C) REVISE ROOF SECTION ON PAGE 2 OF 5. THIS IS NO HIP |
| ROOF AND THERE IS NOT CONCRETE TILE. SEE PLANS. |
| |
| D) REVISE DOORS ON PAGE 3 OF 5. THERE ARE NO WOOD |
| DOORS. SEE PLANS AND PRODUCT APPROVALS. |
| |
| E) REVISE THE WINDOWS SECTION ON PAGE 3 OF 5: * REVISE |
| THE WINDOW ORIENTATION TO MATCH PLANS. ** REVISE THE |
| WINDOW AREAS TO MATCH PLANS. *** REVISE THE OVERHANG |
| DEPTH AND SEPARATION OF EACH WINDOW TO MATCH |
| PLANS/ELEVATIONS. |
| |
| F) OWNER/AGENT TO SIGN AND DATE BOTTOM OR FORM. |
| |
| G) COMPLETE ALL THE INFORMATION ON TOP OF FORM, |
| INCLUDING THE BUILDER'S NAME. |
| |
| 7- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. |
| SEC. 109.3 CITY AMENDMENTS TO FBC. VALUE TO INCLUDE ALL |
| LABOR, MATERIALS, OVERHEAD AND PROFIT AND ALL THE |
| DESIGN PROFESSIONAL FEES. VALUE WAS UPDATED, PERMIT FEE |
| BALANCE IS $2444.70. |
| |
| 8- SPECIFY ON PLANS (INCLUDING IN EXISTING BEDROOMS) |
| CARBON MONOXIDE ALARMS AS REQUIRED BY SEC. R315 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 9- PROVIDE ROOF SHEATHING SPECIFICATIONS. SEC. |
| R803.2.3.1 OF 2010 FBC-RESIDENTIAL AND FIGURE |
| R803.2.3.1. |
| |
| 10- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806. |
| SPECIFY SIZE LOCATION, ETC. INCLUDING THE RIDGE VENT. |
| SEE RIDGE VENT PRODUCT APPROVAL SUBMITTED. |
| |
| 11- SHEET A-2; |
| A) CLARIFY IF INSTALLING NEW KITCHEN. THE LAYOUT IS THE |
| SAME LAYOUT FOR A KITCHEN AND ENERGY CALCULATIONS CALL |
| FOR ADDITION WITH KITCHEN. IDENTIFY THE SPACE WHERE THE |
| NEW "KITCHEN" LAYOUT IS SHOWN. SEC. 107.2.1 CITY |
| AMENDMENTS TO FBC. |
| |
| B) CLARIFY WHY THERE IS A NEW SEWER LINE GOING TO THE |
| CLOSET IN THE ROOM ADJACENT TO THE "NEW STORAGE ROOM". |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| C) IDENTIFY ROOM WITH BAY WINDOWS. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| D) SPECIFY ATTIC ACCESS SIZE: SEC. R807. |
| |
| E) CLARIFY WHY INSTALLING TV, AND PHONE OUTLETS IN "NEW |
| STORAGE ROOM". SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 12- SHEET A-4: CLARIFY WHY ELEVATION #4 SHOWS A "DRYER |
| VENT HOOD". PLANS DON'T SHOW ANY DRYER. SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |
| 13- SHEET S-1; ENGINEER SHOWN ON-THE TITLE BLOCK AT |
| BOTTOM OF SHEET NEEDS TO SIGN AND SEAL DRAWING AS |
| REQUIRED BY SEC. 107.1 CITY AMENDMENTS. |
| |
| |