Plan Review Notes For Permit 13030782 |
Permit Number |
13030782 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-06-25 15:03:24 | ****PROVISO**** | | | | 1. THE AAV'S SHOWN ON P-1.2 & P2.1 WILL BE REQUIRED TO | | BE VENTED AS THEY ARE NOT WITHIN THE TOP FOUR BRANCH | | INTERVALS. | | FBC PLUMBING 917.3.1 | | | | 2. THE CONNECTIONS TO THE SOVENT HORIZONTAL LINE AFTER | | THE DEAERATOR ON P1.2S, P1.3N, P1.3S, AND P2.1 ARE TO | | CONNECT ABOVE THE CENTER LINE. SEE DETAIL # 16 ON P0.3 | | SOVENT RULE B3: | | SOIL AND WASTE CONNECTIONS BETWEEN | | THE CENTER LINE OF THE | | SOVENT STACK AND TERMINATION | | POINT IN THE BUILDING DRAIN IS ALLOWED. | | CONNECTIONS MUST BE | | MADE ABOVE THE CENTER LINE OF THE | | BUILDING DRAIN, OR THE CONNECTIONS | | CAN BE MADE 10 STACK PIPE DIAMETERS | | DOWN STREAM. (DWG. 101-6B) |
|