Date Text
2013-07-10 15:23:51326 FERN STREET
 PERMIT #13030782
 REVIEW #2 COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT/RESUBMIT DRAWINGS ADDRESSING THE
 FIRE REVIEW COMMENTS*****
  
 SHEET A2.00.1: ACCESS TO AN EXIT IS NOT PERMITTED TO BE
 ROUTED THROUGH A STORAGE ROOM ("NEW TENANT STORAGE")
 PER NFPA 101 SECTION 7.5.2.1.
  
  
 ELEVATORS: CONFIRM EXISTING ELEVATORS CONFORM TO THE
 FIREFIGHTERS' EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.3.
  
  
 RESPONSE: THE FIRE DEPARTMENT HAS BEEN REVIEWING AND
 INSPECTING THIS BUILDING AS AN EXISTING HIGH-RISE
 BUILDING; THEREFORE, THE BUILDING AND FIRE CODE
 REQUIREMENTS FOR A "NEW" HIGH-RISE ARE NOT APPLICABLE.
 WITH THAT BEING SAID, THERE ARE CERTAIN SYSTEMS, SUCH
 AS THE FIRE ALARM SYSTEM, THAT NEED TO BE UPGRADED WITH
 THE CHANGE OF OCCUPANCY TO ENSURE THE SAFETY OF THE
 BUILDING OCCUPANTS AND EMERGENCY RESPONDERS. NOTE: THE
 FIRE ALARM DRAWINGS WERE NOT RESUBMITTED FOR REVIEW #2.
  
 REPEAST COMMENT - FIRE ALARM: PER NFPA 101 SECTION
 11.8.4.1, A FIRE ALARM SYSTEM USING AN APPROVED
 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM SHALL BE
 INSTALLED. PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION
 MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN
 REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT, AND
 EXIT THE BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
 REPEAST COMMENT - FIRE ALARM: PER NFPA 101
 SECTION11.8.4.2.1 TWO-WAY TELEPHONE COMMUNICATION
 SERVICE SHALL BE PROVIDED FOR FIRE DEPARTMENT USE. THIS
 SYSTEM SHALL BE IN ACCORDANCE WITH NFPA 72, NATIONAL
 FIRE ALARM CODE. THE COMMUNICATIONS SYSTEM SHALL
 OPERATE BETWEEN THE EMERGENCY COMMAND CENTER AND EVERY
 ELEVATOR CAR, EVERY ELEVATOR LOBBY, AND EACH FLOOR
 LEVEL OF EXIT STAIRS.
  
 REPEAST COMMENT - FIRE ALARM: PLANS DO NOT INDICATE THE
 METHOD (HEAT DETECTOR/FLOW SWITCH WITHOUT TIME DELAY)
 USED TO SHUNT TRIP POWER TO THE ELEVATOR IN THE EVENT
 AN AUTOMATIC SPRINKLER ACTIVATES IN THE ELEVATOR
 MACHINE ROOM.
  
 REPEAST COMMENT - FIRE ALARM: PLANS INDICATE BOTH A
 HEAT AND SMOKE DETECTOR AT THE TOP OF THE ELEVATOR
 SHAFTS. PER NFPA 72 SECTION 21.3.6 (2010 ED), SMOKE
 DETECTORS SHALL NOT BE INSTALLED IN UNSPRINKLERED
 ELEVATOR HOISTWAYS UNLESS THEY ARE INSTALLED TO
 ACTIVATE THE ELEVATOR HOISTWAY SMOKE RELIEF EQUIPMENT.
  
 REPEAST COMMENT - FIRE ALARM: ADD THE WATERFLOW AND
 TAMPER SWITCH SYMBOLS TO THE LEGEND.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730