Date |
Text |
2013-04-04 15:52:15 | |
| FBC 2010 EXISTING BUILDING CODE |
| FBC 2010 ACCESSIBILITY CODE |
| FBC 2010 PLUMBING REVIEW #1 |
| |
| 1. PLEASE SUBMIT THE DATA REQUIRED FOR THE SOVENT |
| SYSTEM. IF THE SOVENT IS CONINE, DE-AERATOR RULE (D): |
| SOIL AND WASTE BRANCHES MAY CONNECT TO THE SOVENT |
| BUILDING DRAIN BETWEEN THE CENTERLINE OF THE STACK AND |
| THE TERMINATION POINT OF THE PRESSURE RELIEF LINE |
| (PRL). ALL CONNECTIONS SHALL BE MADE A MINIMUM DISTANCE |
| OF TEN PIPE |
| DIAMETERS (BASED ON STACK SIZE) DOWNSTREAM FROM THE |
| CENTERLINE OF THE STACK. SOIL AND WASTE BRANCHES SHALL |
| NOT CONNECT |
| WHERE THE SOVENT BUILDING DRAIN MAKES A HORIZONTAL |
| CHANGE OF DIRECTION (EXAMPLE ON P2.1 S6) |
| |
| P-714.4.3 TECHNICAL DATA. THE REGISTERED DESIGN |
| PROFESSIONAL SHALL SUBMIT SUFFICIENT TECHNICAL DATA TO |
| SUBSTANTIATE THE PROPOSED ALTERNATIVE ENGINEERED DESIGN |
| AND TO PROVE THAT THE PERFORMANCE MEETS THE INTENT OF |
| THIS CODE. |
| |
| 2. SHEET A4.10 THE COMMON AREA TOILET ROOMS ARE TO BE |
| BETWEEN 16" - 18" MAX. OFF THE SIDE WALL. ACCESSABILITY |
| 604.2 LOCATION. |
| |
| *PROVISO* |
| FOR THE DOMESTIC PUMPS SHOWN ON P0.2: |
| 606.5.5 LOW-PRESSURE CUTOFF REQUIRED ON BOOSTER PUMPS. |
| A LOW-PRESSURE CUTOFF SHALL BE INSTALLED ON ALL BOOSTER |
| PUMPS IN A WATER PRESSURE BOOSTER SYSTEM TO PREVENT |
| CREATION OF A VACUUM OR NEGATIVE PRESSURE ON THE |
| SUCTION SIDE OF THE PUMP WHEN A POSITIVE PRESSURE OF 10 |
| PSI (68.94 KPA) OR LESS OCCURS ON THE SUCTION SIDE OF |
| THE PUMP. |
| |
| REVIEW BY |
| LARRY WAGNER |
| CHIEF PLUMBING INSPECTOR |
| PHONE # 805-6692 |
| EMAIL [email protected] |
| FAX # 805-6676 |
| |