Plan Review Notes For Permit 13030782
Permit Number 13030782
Review Stop P
Sequence Number 1
Notes
Date Text
2013-04-04 15:52:15 
 FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
  
 1. PLEASE SUBMIT THE DATA REQUIRED FOR THE SOVENT
 SYSTEM. IF THE SOVENT IS CONINE, DE-AERATOR RULE (D):
 SOIL AND WASTE BRANCHES MAY CONNECT TO THE SOVENT
 BUILDING DRAIN BETWEEN THE CENTERLINE OF THE STACK AND
 THE TERMINATION POINT OF THE PRESSURE RELIEF LINE
 (PRL). ALL CONNECTIONS SHALL BE MADE A MINIMUM DISTANCE
 OF TEN PIPE
 DIAMETERS (BASED ON STACK SIZE) DOWNSTREAM FROM THE
 CENTERLINE OF THE STACK. SOIL AND WASTE BRANCHES SHALL
 NOT CONNECT
 WHERE THE SOVENT BUILDING DRAIN MAKES A HORIZONTAL
 CHANGE OF DIRECTION (EXAMPLE ON P2.1 S6)
  
 P-714.4.3 TECHNICAL DATA. THE REGISTERED DESIGN
 PROFESSIONAL SHALL SUBMIT SUFFICIENT TECHNICAL DATA TO
 SUBSTANTIATE THE PROPOSED ALTERNATIVE ENGINEERED DESIGN
 AND TO PROVE THAT THE PERFORMANCE MEETS THE INTENT OF
 THIS CODE.
  
 2. SHEET A4.10 THE COMMON AREA TOILET ROOMS ARE TO BE
 BETWEEN 16" - 18" MAX. OFF THE SIDE WALL. ACCESSABILITY
 604.2 LOCATION.
  
 *PROVISO*
 FOR THE DOMESTIC PUMPS SHOWN ON P0.2:
 606.5.5 LOW-PRESSURE CUTOFF REQUIRED ON BOOSTER PUMPS.
 A LOW-PRESSURE CUTOFF SHALL BE INSTALLED ON ALL BOOSTER
 PUMPS IN A WATER PRESSURE BOOSTER SYSTEM TO PREVENT
 CREATION OF A VACUUM OR NEGATIVE PRESSURE ON THE
 SUCTION SIDE OF THE PUMP WHEN A POSITIVE PRESSURE OF 10
 PSI (68.94 KPA) OR LESS OCCURS ON THE SUCTION SIDE OF
 THE PUMP.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  