Plan Review Notes For Permit 13030782 |
Permit Number |
13030782 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-04-05 13:59:13 | PLANS DENIED | | 1) REFER TO SECTION 607.5.5 SHAFT ENCLOSURES | | 2010 FBC (M) | | 2) DUCT PENETRATING STAIR WELL PAGE M1.25. REFER TO | | SECTION | | 1022.4 FBC | | 3) MISSING SMOKE FIRE DAMPER IN SHAFT BY TRASH ROOM | | PAGE M 1.25 | | PER SECTION 607 FBC (M) 2010 | | 4) REFER TO SECTION 713.3 FIRE RESISTANCE RATED WALLS | | FBC 2010 | | PROVIDE A DETAIL ON THE PLANS ON HOW YOU WILL PROTECT | | THE PENETRATIONS | | OF THE EXHAUST AND FREON LINES IN THE RATED WALLS. | | 5) PROVIDE A DETAIL ON THE PLANS FOR THE CURB TO ROOF | | TIEDOWN. | | PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M) . | | 6) PROVIDE EQUIPMENT SCHEDULE ON THE PLANS. | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|