Plan Review Notes
Plan Review Notes For Permit 13030782
Permit Number 13030782
Review Stop M
Sequence Number 1
Notes
Date Text
2013-04-05 13:59:13PLANS DENIED
 1) REFER TO SECTION 607.5.5 SHAFT ENCLOSURES
 2010 FBC (M)
 2) DUCT PENETRATING STAIR WELL PAGE M1.25. REFER TO
 SECTION
 1022.4 FBC
 3) MISSING SMOKE FIRE DAMPER IN SHAFT BY TRASH ROOM
 PAGE M 1.25
 PER SECTION 607 FBC (M) 2010
 4) REFER TO SECTION 713.3 FIRE RESISTANCE RATED WALLS
 FBC 2010
 PROVIDE A DETAIL ON THE PLANS ON HOW YOU WILL PROTECT
 THE PENETRATIONS
 OF THE EXHAUST AND FREON LINES IN THE RATED WALLS.
 5) PROVIDE A DETAIL ON THE PLANS FOR THE CURB TO ROOF
 TIEDOWN.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M) .
 6) PROVIDE EQUIPMENT SCHEDULE ON THE PLANS.