2013-04-03 13:43:17 | 326 FERN STREET |
| PERMIT #13030782 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| *****THIS IS A CHANGE OF OCCUPANCY FROM BUSINESS TO |
| APARTMENT OCCUPANCY***** |
| |
| NOTE: ANY REFERENCE TO NFPA 101 - THE LIFE SAFETY CODE |
| IS REFERRING TO THE 2010 EDITION OF THE FLORIDA FIRE |
| PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF NFPA |
| 101 WITH FLORIDA AMENDMENTS. |
| |
| |
| GENERAL: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE |
| DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE |
| EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR |
| MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING |
| SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH |
| REQUESTS MUST BE SUBMITTED IN WRITING (FAX: |
| 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| |
| GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| ORDERED FROM WWW.KNOXBOX.COM. |
| |
| SITE: THE EXISTING SPRINKLER SYSTEM FIRE DEPARTMENT |
| CONNECTION IS SURFACE MOUNTED (FERN STREET) ON THE FACE |
| OF THE BUILDING. THE CURRENT PARKING SPACE AND METER |
| NEEDS TO BE REMOVED AND THE SPACE SHOULD BE IDENTIFIED |
| WITH A PERMAMENT FREE STANDING SIGN INDICATING, "FDC - |
| NO PARKING BY ORDER OF THE FIRE MARSHAL." SIGN SHALL BE |
| 12" X 18" WITH A WHITE BACKGROUND AND RED LETTERS AND |
| SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE |
| BOTTOM OF THE SIGN. |
| |
| GENERAL: PER NFPA 101 SECTION 7.2.2.5.4 - STAIRWAY |
| IDENTIFICATION: NEW ENCLOSED STAIRS SERVING THREE OR |
| MORE STORIES AND EXISTING ENCLOSED STAIRS SERVING FIVE |
| OR MORE STORIES SHALL COMPLY WITH (A) THROUGH (L). |
| (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE |
| WITHIN THE ENCLOSURE AT EACH FLOOR LANDING. |
| (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL. |
| (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP |
| AND BOTTOM OF THE STAIR ENCLOSURE. |
| (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF |
| THE STAIR ENCLOSURE. |
| (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND |
| THE DIRECTION TO, EXIT DISCHARGE. |
| (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE |
| APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A |
| POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN |
| OR CLOSED POSITION. |
| (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE. |
| (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE |
| WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE |
| WALL. |
| (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED |
| AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH |
| LETTERING. |
| (J) SIGNAGE THAT READS "NO ROOF ACCESS" AND IS LOCATED |
| UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL |
| DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS. |
| LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH. |
| (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE |
| MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS. |
| MEZZANINE LEVELS SHALL HAVE THE LETTER "M" OR OTHER |
| APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR |
| NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER "B" |
| OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING |
| THE FLOOR LEVEL NUMBER. |
| (M) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF |
| THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN |
| IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS. |
| |
| ELEVATORS: CONFIRM EXISTING ELEVATORS CONFORM TO THE |
| FIREFIGHTERS' EMERGENCY OPERATIONS REQUIREMENTS OF ASME |
| A17.3. |
| |
| SHEET A0.01: PROVIDE BUILDING ADDRESS VISIBLE FROM THE |
| STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING AND |
| BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND |
| SHALL CONTRAST THE BACKGROUND PER NFPA 1 SECTION |
| 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA 1. |
| |
| SHEET A2.00.1LS: PER NFPA 101 SECTION 7.2.2.5.4.2: |
| WHEREVER AN ENCLOSED STAIR REQUIRES TRAVEL IN AN UPWARD |
| DIRECTION TO REACH THE LEVEL OF EXIT DISCHARGE, SPECIAL |
| SIGNS WITH DIRECTIONAL INDICATORS SHOWING THE DIRECTION |
| TO THE LEVEL OF EXIT DISCHARGE SHALL BE PROVIDED AT |
| EACH FLOOR LEVEL LANDING FROM WHICH UPWARD DIRECTION OF |
| TRAVEL IS REQUIRED. |
| |
| SHEET A2.00.1LS: PER NFPA 101 SECTION 9.4.7 ELEVATORS |
| SHALL NOT OPEN INTO AN EXIT ENCLOSURE. |
| |
| SHEET A2.00.2LS: RETAIL #100 IS INDICATED AS POSSIBLY |
| BEING A FUTURE RESTAURANT. THIS WILL CHANGE THE |
| OCCUPANCY FROM MERCANTILE TO ASSEMBLY REQUIRING TWO |
| SEPARATE EXITS. THE CURRENT EXITING SCHEME SHOWS THE |
| SECONDARY EXIT ROUTED THROUGH THE RESIDENTIAL LOBBY |
| WHICH WOULD NOT BE PERMITTED UTILIZING A DESIGN OF |
| "SEPARATED MIXED-USE." NOTE: THE MERCANTILE OCCUPANCY |
| REQUIRES ONLY ONE EXIT SO THE CURRENT LAYOUT IS NOT AN |
| ISSUE. |
| |
| SHEET A2.00.2LS: PER NFPA 101 SECTION 7.5.1.1.1, WHERE |
| EXITS ARE NOT IMMEDIATELY ACCESSIBLE FROM AN OPEN FLOOR |
| AREA, CONTINUOUS PASSAGEWAYS, AISLES, OR CORRIDORS |
| LEADING DIRECTLY TO EVERY EXIT SHALL BE MAINTAINED AND |
| SHALL BE ARRANGED TO PROVIDE ACCESS FOR EACH OCCUPANT |
| TO NOT LESS THAN TWO EXITS BY SEPARATE WAYS OF TRAVEL. |
| CORRIDOR #C101 DOES NOT APPEAR TO HAVE A FIRE |
| RESISTANCE RATING ALL THE WAY TO THE EXIT DOOR. PER |
| NFPA 101 SECTION 30.3.6.1.2, IN BUILDINGS PROTECTED |
| THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| SPRINKLER SYSTEM, CORRIDOR WALLS SHALL HAVE A MINIMUM |
| 1/2-HOUR FIRE RESISTANCE RATING AND DOORS THAT OPEN |
| ONTO EXIT ACCESS CORRIDORS SHALL HAVE NOT LESS THAN A |
| 20-MINUTE FIRE PROTECTION RATING. PROTECT ALL OPENINGS |
| AND PENETRATIONS. |
| |
| SHEET A2.00.2LS: ANOTHER EXIT SIGN IS NEEDED AT THE TOP |
| OF THE SMALL STAIR ADJACENT TO THE WHEELCHAIR LIFT IN |
| CORRIDOR #C101. |
| |
| SHEET A2.00.2LS: RETAIL #100 - ALL EXTERIOR DOORS NOT |
| FUNCTIONING AS EXITS SHALL BE PERMANENTLY MARKED AND |
| CLEARLY INDICATED AS, "NOT AN EXIT." |
| |
| SHEET A2.00.2LS: COMMUNITY ROOM #102 - TABLES AND |
| CHAIRS ARE OBSTRUCTING THE EXIT DOORS. |
| |
| SHEET A2.00.2LS: LAUNDRY ROOM (#115) LARGER THAN 100 |
| SQ.FT. SHALL BE SEPARATED FROM OTHER AREAS BY A 1-HOUR |
| FIRE RATED BARRIER PER TABLE 30.3.2.1.1 OF NFPA 101. |
| PROTECT ALL OPENINGS AND PENETRATIONS. |
| |
| SHEET A4.02S: DOOR (#1) LOCATED IN STAIR ENCLOSURE |
| VESTIBULE (C104) NEEDS A FIRE RESISTANCE RATING OF |
| 90-MINUTES. ALSO CONFIRM VESTIBULE IS FIRE RATED FOR |
| 2-HOURS. |
| |
| SHEET A4.02S: ELECTRICAL ROOM DOORS SHALL BE EQUIPPED |
| WITH PANIC/FIRE EXIT HARDWARE PER NFPA 70 SECTION |
| 110.26. |
| |
| SHEET M1.2N: FIRE DAMPERS WILL BE NEEDED FOR DUCTWORK |
| PENETRATING LAUNDRY ROOM WALLS. LAUNDRY ROOM (#115) |
| LARGER THAN 100 SQ.FT. SHALL BE SEPARATED FROM OTHER |
| AREAS BY A 1-HOUR FIRE RATED BARRIER PER TABLE |
| 30.3.2.1.1 OF NFPA 101. |
| |
| SHEET M1.2N: UNPROTECTED EXHAUST DUCT IS ROUTED THROUGH |
| A 2-HOUR FIRE BARRIER. EXHAUST DUCT IS SERVING ADJACENT |
| RETAIL SPACE BATHROOM. |
| |
| SHEET E0.1: "ELECTRICAL RESIDENTIAL UNIT NOTES" #2 |
| INDICATES THAT THE SMOKE/CARBON MONOXIDE ALARMS SHALL |
| BE TIED INTO THE THE FIRE ALARM SYSTEM. THE SMOKE/CO |
| ALARMS IN THE INDIVIDUAL APARTMENT UNITS SHALL BE LOCAL |
| ALARM ONLY AND SHALL NOT RESULT IN ACTIVATION OF THE |
| BUILDING FIRE ALARM SYSTEM. |
| |
| SHEET E1.2S: SMOKE ALARM OMITTED FROM RESIDENTIAL UNIT |
| #105. |
| |
| FIRE ALARM: PER NFPA 101 SECTION 11.8.4.1, A FIRE ALARM |
| SYSTEM USING AN APPROVED EMERGENCY VOICE/ALARM |
| COMMUNICATION SYSTEM SHALL BE INSTALLED. PROVIDE A |
| PRE-RECORDED FIRE ALARM EVACUATION MESSAGE NOTIFYING |
| OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN THE |
| BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE |
| BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR. |
| |
| FIRE ALARM: PER NFPA 101 SECTION11.8.4.2.1 TWO-WAY |
| TELEPHONE COMMUNICATION SERVICE SHALL BE PROVIDED FOR |
| FIRE DEPARTMENT USE. THIS SYSTEM SHALL BE IN ACCORDANCE |
| WITH NFPA 72, NATIONAL FIRE ALARM CODE. THE |
| COMMUNICATIONS SYSTEM SHALL OPERATE BETWEEN THE |
| EMERGENCY COMMAND CENTER AND EVERY ELEVATOR CAR, EVERY |
| ELEVATOR LOBBY, AND EACH FLOOR LEVEL OF EXIT STAIRS. |
| |
| FIRE ALARM: PLANS DO NOT INDICATE THE METHOD (HEAT |
| DETECTOR/FLOW SWITCH WITHOUT TIME DELAY) USED TO SHUNT |
| TRIP POWER TO THE ELEVATOR IN THE EVENT AN AUTOMATIC |
| SPRINKLER ACTIVATES IN THE ELEVATOR MACHINE ROOM. |
| |
| FIRE ALARM: PLANS INDICATE BOTH A HEAT AND SMOKE |
| DETECTOR AT THE TOP OF THE ELEVATOR SHAFTS. PER NFPA 72 |
| SECTION 21.3.6 (2010 ED), SMOKE DETECTORS SHALL NOT BE |
| INSTALLED IN UNSPRINKLERED ELEVATOR HOISTWAYS UNLESS |
| THEY ARE INSTALLED TO ACTIVATE THE ELEVATOR HOISTWAY |
| SMOKE RELIEF EQUIPMENT. |
| |
| FIRE ALARM: ADD THE WATERFLOW AND TAMPER SWITCH SYMBOLS |
| TO THE LEGEND. |
| |
| FIRE ALARM: PROVIDE NOTIFICATION APPLIANCE IN LAUNDRY |
| ROOM #115. |
| |