2013-04-17 16:58:52 | BUILDING PLAN REVIEW |
| PERMIT: 13030782 |
| ADD: 326 FERN ST |
| CONT: STRATICON, LLC |
| TEL: (772)210-0200 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: APRIL 17/ 2013 |
| ACTION: DENIED |
| |
| 1) SHEET A0.01: |
| 1A) PLEASE REVISE THE GENERAL PROJECT INFORMATION NOTE, |
| THAT INDICATES THE SCOPE OF THESE DRAWINGS ARE FOR |
| INTERIOR DEMOLITION ONLY. |
| |
| 1B) PROJECT SPECIFIC CODE SUMMARY INDICATE THIS PROJECT |
| WAS DESIGNED AS A LEVEL II ALTERATION. PLEASE REFER TO |
| THE 2010 EXISTING BUILDING CODE SECTION 901.3 CHANGE OF |
| OCCUPANCY CLASSIFICATION. WHERE THE OCCUPANCY |
| CLASSIFICATION OF A BUILDING CHANGES, THE PROVISIONS OF |
| SECTIONS 902 THROUGH 912 SHALL APPLY. THIS INCLUDES A |
| CHANGE OF OCCUPANCY CLASSIFICATION WITHIN A GROUP AS |
| WELL AS A CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE |
| GROUP TO A DIFFERENT GROUP. |
| |
| 1C) THIS STRUCTURE IS ALSO CLASSIFIED AS A HISTORIC |
| STUCRTURE PLEASE INDICATE WHICH METHOD OF COMPLIANCE |
| YOU WOULD BE CLAIMING UNDER THE HISTORICAL DESIGNATION. |
| SECTION 1104 EQUIVALENCY, SECTION 1105 COMPLIANCE OR |
| SECTION 1106 INVESTIGATION AND EVALUATION. |
| |
| 1D) THE COVERSHEET ALSO REFERENECES THE PALM BEACH |
| COUNTY AMENDMENTS. THE PALM BEACH COUNTY AMENDMENTS |
| WILL ONLY PERTAIN TO |
| CHAPTER 1 AND ONLY IF THIS PROJECT WAS LOCATED IN THE |
| COUNTY. THE CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| PLEASE UPDATE. |
| |
| 1E) THE FINISH FLOOR OF THE SIXTH FLOOR IS 76'-0" ABOVE |
| GRADE AND MEETS THE DEFINITION OF HIGHRISE DEFINITION |
| 202 FBC-B. |
| |
| 2) THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING. |
| THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| PERSONS. |
| |
| 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL |
| INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| |
| 2B) THRESHOLD INSPECTOR: |
| WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| CODE. |
| CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| BEFORE THE PERMIT MAY BE ISSUED. |
| |
| 2C) THRESHOLD BLDG, REQUIRED STATEMENT: |
| W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| |
| ------------------------------------------------------- |
| ----------------------------------- |
| |
| 2D) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| WALLS AND CEILINGS. |
| ------------------------------------------------------- |
| ------------------------------------- |
| |
| 2E) A THRESHOLD PLAN REVIEW STOP WILL BE ADDED TO THE |
| PLAN REVIEW FOR THIS PROJECT UNTIL THESE ITEMS ARE |
| COMPLETED AS REQUESTED BY THE CHIEF BUILDING INSPECTOR |
| KEN CONRAD: |
| |
| PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| 2E)(1)) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| CONRAD: [email protected] |
| |
| 2E)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A |
| RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. |
| THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| CONTACT KEN CONRAD |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| 3) SHEET A2.001 LS- BASEMENT: |
| 3A) THE STAIRWELL # 1 HAS THE ELEVATOR LOCATED IN THE |
| VERTICAL EXIT. 2010 EXISTING BUILDING CODE |
| 912.1.1COMPLIANCE WITH CHAPTER 8. |
| SEE COMPLIANCE WITH 801.2 COMPLIANCE. IN ADDITION TO |
| THE PROVISIONS OF THIS CHAPTER, WORK SHALL COMPLY WITH |
| ALL OF THE REQUIREMENTS OF CHAPTERS 6 AND 7. THE |
| REQUIREMENTS OF SECTIONS 703, 704, AND 705 SHALL APPLY |
| WITHIN ALL WORK AREAS WHETHER OR NOT THEY INCLUDE EXITS |
| AND CORRIDORS SHARED BY MORE THAN ONE TENANT AND |
| REGARDLESS OF THE OCCUPANT LOAD. 703.2.1 EXISTING |
| VERTICAL OPENINGS. |
| ALL EXISTING INTERIOR VERTICAL OPENINGS CONNECTING TWO |
| OR MORE FLOORS SHALL COMPLY WITH THE APPROPRIATE |
| SECTIONS OF THE FLORIDA FIRE PREVENTION CODE. 2010 |
| FBC-B 10.22.3 ELEVATORS SHALL NOT OPEN INTO AN EXIT |
| ENCLOSURE. |
| |
| 3B) NEITHER THIS SHEET NOR A2.01 SHOW THE WALLS OR |
| OPENING PROTECTIVES TO BE FIRE RATED BARRIERS. 2010 |
| FBC-B 913.2.1 PROTECTION OF FIRE PUMP ROOMS. |
| FIRE PUMPS SHALL BE LOCATED IN ROOMS THAT ARE SEPARATED |
| FROM ALL OTHER AREAS OF THE BUILDING BY 2-HOUR FIRE |
| BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR |
| 2-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE |
| WITH SECTION 712, OR BOTH. EXISTING BUILDING CODE |
| 912..2 FIRE PROTECTION SYSTEMS. |
| |
| 4) SHEET A2.002 LS- 1ST FLOOR: |
| 4A) FIRE COMMAND ROOM FBC-B 403.4.5 SEE SECTION 911 1 |
| HOUR FIRE SEPERATION. |
| |
| 4B) THE AREA LISTED AS MERCANTILE OR RESTARAUNT MAY |
| ALSO MEET THE OCCUPANCY LOAD FOR AN A2 ASSEMBLY IF THE |
| OCCUPANT LOAD IS OVER 50. |
| THE IF THE RESTARAUNT IS LESS THAN 50 IT WILL BE |
| CONSIDERED MERCANTILE. THE OCCUPANT LOADING FOR |
| MERCANTILE AT GRADE IS 30 SQ FT / OCCUPANT BUT THE A2 |
| ASSEMBLY IS FIGURED AT 15 SQ FT / OCCUPANT IF THE SPACE |
| IS GOING TO SELL GROCERCIES IT WILL BE CONSIDERED |
| MERCANTILE |
| BUT IF THE RENTAL SPACE WILL BE CONSIDERED A RESTARAUNT |
| USE THE 15 SQ FT /OCCUPANT. 2010 FBC-B TABLE 1004.1.1. |
| |
| 4C) THE OCCUPANCY SEPERATION WALL BETWEEN THE R2 |
| OCCUPANCY AND THE BUSINESS & ASSEMBLY (COMMUNITY ROOM # |
| 102) IS NOT A CONTINIOUS SEPERATION AND OR OPENING |
| PROTECTIVES, PLEASE IDENTIFY? 2010 FBC-B TABLE 508.4 & |
| TABLE 715.4. |
| |
| 4D) FOR BOTH VERTICAL EXITS THAT OPEN ONTO THIS FLOOR |
| AND THEN CONTINUE INTO THE BASEMENT, PLEASE PLACE EXIT |
| DIRECTIONAL SIGNAGE PER |
| (2010 FBC-B 1022.7) TO PREVENT PERSONS FROM |
| UNINTENIONALLY CONTINUING INTO LEVELS BELOW GRADE. |
| |
| 4E) ALSO REVIEW FBC-B 1009.6.4 STAIR IDENTIFICATION & |
| 1022.8 FLOOR IDENTIFICATION. |
| |
| 4F) CODE ANALYSIS NOTE # 5 INDICATES SOUND TRANSMITION |
| FBC-B1207.2 BUT NO COMMENT TO FBC-B 1207.3 AND |
| COMPLIANCE WITH : |
| 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 5) SHEET A2.00.3 LS 2ND FLOOR: |
| 5A) COMMON STATEMENT FOR THE 2ND -6TH FLOOR. PLANS ARE |
| MISSING THE ELEVATOR LOBBY FBC-B 708.14.1. 2010 |
| EXISTING BLDG CODE SECTION |
| 703.2.2. SUPPLEMENTAL SHAFT AND FLOOR OPENING ENCLOSURE |
| REQUIREMENTS. WHERE THE WORK AREA ON ANY FLOOR EXCEEDS |
| 50 PERCENT OF THAT FLOOR AREA, THE ENCLOSURE |
| REQUIREMENTS OF SECTION 703.2 SHALL APPLY TO VERTICAL |
| OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE FLOOR. |
| |
| 5B) COMMON STATEMENT FOR THE 2ND -6TH FLOOR AT GRID |
| LINES E BETWEEN 4 &5. THIS AREA IS SHARED BETWEEN 3 |
| TENANTS, THE CONCERN IS IF A FIRE IS STARTED WITHIN |
| THIS AREA THE THREE UNITS WILL BE EFFECTED BY NOT |
| HAVING FIRE RATED GLASS IN THE WINDOWS & DOORS. THE |
| PLANS DO STATE THESE OPENINGS WILL HAVE LARGE MISSILE |
| IMPACT RESISTANT GLAZING IN THE OPENINGS, WE WOULD BE |
| LESSS CONCERNED WITH THE FIRE RATED GLASS IF THIS AREA |
| IS TO BE FIRE SPRINKLERED SINCE THERE ARE CURRENTLY NO |
| FIRE SPRINKLER PLANS THAT WERE SUBMITTED IN THIS SET OF |
| PLANS. FBC-B 403.3. |
| |
| 6) SHEET A3.01.1 & A3.01.2ELEVATIONS, PRESSURES & |
| PRODUCT APPROVALS: |
| 6A) THE LIST OF PRODUCT APPROVALS IS NOT ENOUGH TO BE |
| ABLE TO DO A COMPLETE REVIEW OF THE LISTED PRODUCTS. |
| THE CITY WILL REQUIRE PRODUCT APPROVALS FOR ALL |
| COMPONENTS AND CLADDING THAT WILL BE INSTALLED ON THE |
| EXTERIOR OF THIS PROJECT. A LIST IS NOT SUFFICIENT |
| ENOUGH, TO BE ABLE TO DO A REVIEW OF THE PRODUCT. (3) |
| COPIES OF EACH PRODUCT WILL BE REQUIRED SINCE THIS IS A |
| THRESHOLD BUILDING. 2010 WPB ADMIN CODE 107.3 |
| EXAMINATION OF DOCUMENTS/ 2010 FBC-B 1609.6.4.4.1. |
| COMPONENTS & CLADDING. |
| |
| 6B) FOR GLAZING PRODUCT APPROVALS PLEASE CIRCLE THE |
| LENGTH, WIDTH, TYPE OF GLAZING, MULLIONS AND PRESSURES |
| SO WE WILL KNOW WHICH OPTIONS YOU ARE SELECTING. |
| |
| 6C) ROOFING PRODUCT APPROVALS, WILL HAVE VARIOUS |
| SUB-SYSTEMS THAT CAN BE INSTALLED UNDER VARYING |
| CONDITIONS AND ASSOCATED PRESSURES. PLEASE HIGHLIGHT |
| WHICH OF THESE SUB-SYSTEMS WILL BE INSTALLED ON THIS |
| PROJECT, IF MORE THAN ONE SUB-SYSTEM WILL BE INSTALLED |
| PLEASE IDENTIFY EACH AND THE LOCATION OF THE |
| INSTALATION. NOTE IF THE PRODUCT APPROVALS HAS |
| LIMITATIONS ON ENHANCED FASTENING IN ZONES 2 & 3. IF |
| ALLOWED PROVIDE RAS 117 CALCULATIONS PREPARED BY A |
| DESIGN PROFESSIONAL. 1609.6.4.3. |
| |
| 6D) PLEASE NOTE THE LISTED PRODUCT NOA 09-0804.05 ROOF |
| TOP A/C RACK +/- 75 , SHEET S0.02 INDICATES TTHE ROOF |
| TOP PRESSUES IN VULT |
| ZONE 1 VULT -122.1= -73,26 VASD |
| ZONE 2 &3 VULT -191.7= -115.02 VASD |
| PLEASE ALSO REVIEW FBC-B 1609.8 FOR ROOF TOP STRUCTURES |
| AND EQUIPMENT AAND MULTIPLIERS TO BE USED. |
| IT APPEARS THIS PRODUCT WILL NOT MEET THE ASSOCIATED |
| PRESSURES FOR ANY ZONE. THERE ARE ALOT OF A/C ROOFTOP |
| UNITS THAT ARE LOCATED WITHIN ZONE 2 WITH THE INCREASED |
| PRESSURES. |
| |
| 6E) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 6F) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 |
| NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES ROOFTOP EQUIPMENT/ |
| EXHAUST FANS |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STANDS |
| |
| 6G) SHEET SHEET A3.01.2 DETAIL SOUTH ELEVATION BALCONY |
| AREA, PLEASE PROVIDE A SUMMARY OF PRESSURES FOR THE |
| INSET BALCONY AREA. WIND DESIGN IS TO BE TAKEN FORM ALL |
| DIRECTIONS, IF SUCH WHEN THE WIND WOULD BE FROM THE |
| SOUTHEAST THIS AREA IS LIKE A PARTIALLY ENCLOSED |
| BUILDING THAT WILL ALLOW THE WIND TO ENTER AND |
| PRESSUREIZE THIS AREA GREATER THAN THE SURROUNDING |
| SURFACES WHERE THE WIND WOULD BE ABLE TO RACE ACROSS |
| THE FRONT. THE SECOND EFFECT IS IF THE WIND DIRECTION |
| IS FROM THE NORTH EAST WHERE A VENTURI-EFFECT TAKES |
| PLACE SIMILAR TO AN END ZONE WHERE THE NEGATIVE |
| PRESSURES WILL BE HIGHER? 1609.4.1 WIND DIRECTION AAND |
| SECTORS. |
| |
| 7) SHEET A4.02N DOOR # 21A IS MISSING FIRE RATING PER |
| FBC-B 911.1.2 OPENING PROTECTION TABLE 715.4. |
| |
| 8SHEET A4.02S DOOR # 19 STAAIRWELL DOOR MISSING FIRE |
| RATING OPENING PROTECTIVES T 715.4. |
| |
| 9) SHEET A4-10 : |
| 9A) LOBBY TOILET ROOM INDICATES THE ACCESSIBLE WATER |
| CLOSET IS 1'-8" AWAY FROM THE SIDE WALL NOT 18" PLEASE |
| SEE 2010 FL ACC CODE 604.2. |
| |
| 9B) DETAIL # 7 RETAIL WATER CLOSET ROOM IS INDICATED TO |
| BE 2'-0" AWAY FROM THE SIDE WALL. 2010 FL ACC CODE |
| 604.2. |
| |
| 10) A8.01 DETAIL 4 WALL TYPE A.4 DOES NOT PROVIDE THE |
| FBC-B 1207.2 AIR-BORNE SOUND. |
| |
| 11) SHEET A8.02 WINDOW BUCK DETAILS INDICATE A BEVELED |
| BUCK THAT DOES NOT EXTEND TO THE BACK WINDOW FLANGE, NO |
| SUPPORT. FBC-B 1715.5.4.2 MASONRY, CONCRETE OR OTHER |
| STRUCTURAL SUBSTRATE. UNLESS OTHERWISE TESTED, BUCKS |
| SHALL EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR |
| DOOR FRAME SUCH THAT FULL SUPPORT OF THE FRAME IS |
| PROVIDED. SHIMS SHALL BE MADE FROM MATERIALS CAPABLE OF |
| SUSTAINING APPLICABLE LOADS, LOCATED AND APPLIED IN A |
| THICKNESS CAPABLE OF SUSTAINING APPLICABLE LOADS. |
| ANCHORS SHALL BE PROVIDED TO TRANSFER LOAD FROM THE |
| WINDOW OR DOOR FRAME ASSEMBLY TO THE SECURED WOOD BUCK. |
| |
| 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |