Date Text
2013-03-27 16:53:542010 FBC
  
 DENIED BY BUILDING
  
 1) THE MAXIMUM UPLIFT PRESSURE OF -71 PSF FROM THE
 METAL ROOF PRODUCT APPROVALS ARE TOO LOW FOR THIS
 PROJECT. THIS STRUCTURE IS LOCATED IN A 17O MPH VULT /
 132 MPH VASD WIND SPEED AND EXPOSURE CATEGORY D. PLEASE
 SUBMIT PRODUCT APPROVALS WITH ADEQUATE UPLIFT
 PRESSURES. DCA RULE 9N-3 AND FBC R301.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]