Plan Review Notes
Plan Review Notes For Permit 13030713
Permit Number 13030713
Review Stop M
Sequence Number 1
Notes
Date Text
2013-05-14 13:50:48PER PHONE CONVERSATION WITH MR. MESARIC FROM "Z"
 STUDIO. MECHANICAL CONTRACTOR WILL PROVIDE COMPLETE AND
 CORRECT INFORMATION UNDER SEPARATE MECHANICAL PERMIT.
  
 A) INFORMATION ON EQUIPMENT SIZING CALCULATIONS TO
 MATCH INFORMATION ON A/C PLAN AND THE ENERGY
 CALCULATIONS (SIZE OF UNIT AND SEER). B) WHY ROOF
 GAIN/LOSS IS 0%?. C) THERE IS NOT NATURAL GAS FURNACE
 ON PLANS. D) PAGE 9 OF EQUIPMENT CALCULATIONS TO
 INCLUDE ALL THE EQUIPMENT INFORMATION. E) WHY EQUIPMENT
 CALCULATIONS CALL FOR 4 REGISTERS. THIS IS A MINI-SPLIT
 UNIT. F) WHY EQUIPMENT CALCULATIONS ARE CONSIDERING
 DUCTWORK. THIS IS A DUCTLESS UNIT. G) REVISE TOTAL
 BUILDING SUMMARY LOADS ON PAGE 6 OF EQUIPMENT SIZING
 CALCULATIONS. NEED TO MATCH INFORMATION ON PLANS. THERE
 IS IS NOT CRAWL SPACE, ROOF INSULATION IS R19, ETC.