Plan Review Notes For Permit 13030713 |
Permit Number |
13030713 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-05-14 13:50:48 | PER PHONE CONVERSATION WITH MR. MESARIC FROM "Z" | | STUDIO. MECHANICAL CONTRACTOR WILL PROVIDE COMPLETE AND | | CORRECT INFORMATION UNDER SEPARATE MECHANICAL PERMIT. | | | | A) INFORMATION ON EQUIPMENT SIZING CALCULATIONS TO | | MATCH INFORMATION ON A/C PLAN AND THE ENERGY | | CALCULATIONS (SIZE OF UNIT AND SEER). B) WHY ROOF | | GAIN/LOSS IS 0%?. C) THERE IS NOT NATURAL GAS FURNACE | | ON PLANS. D) PAGE 9 OF EQUIPMENT CALCULATIONS TO | | INCLUDE ALL THE EQUIPMENT INFORMATION. E) WHY EQUIPMENT | | CALCULATIONS CALL FOR 4 REGISTERS. THIS IS A MINI-SPLIT | | UNIT. F) WHY EQUIPMENT CALCULATIONS ARE CONSIDERING | | DUCTWORK. THIS IS A DUCTLESS UNIT. G) REVISE TOTAL | | BUILDING SUMMARY LOADS ON PAGE 6 OF EQUIPMENT SIZING | | CALCULATIONS. NEED TO MATCH INFORMATION ON PLANS. THERE | | IS IS NOT CRAWL SPACE, ROOF INSULATION IS R19, ETC. |
|