2013-04-01 17:02:48 | 13030713 | | 216 BEVERLY ROAD | | SFD ADDITION | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | PROVIDE AN ELECTRICAL RISER PLAN FOR THE SERVICE. SHOW | | THE LOCATION OF THE ELECTRICAL SERVICE AND EXISTING | | PANEL WITH MAIN DISCONNECT. SHOW THE EXISTING AND NEW | | FEEDERS. SHOW THE PANEL SCHEDULES. INCLUDE A LOAD | | CALCULATION. NEC 215.5 | | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | SERVICE GROUND. NEC 250.94 | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|