Plan Review Notes
Plan Review Notes For Permit 13030713
Permit Number 13030713
Review Stop B
Sequence Number 1
Notes
Date Text
2013-03-29 17:12:40RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES). SEC. 103.2
 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION TO INCLUDE
 ALL THE LABOR, MATERIALS, ALL DESIGN PROFESSIONAL FEES
 AND OVERHEAD AND PROFIT. VALUE WAS UPDATED TO $43,843.
 PERMIT FEE BALANCE IS $1216.11.
  
 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 4- CLARIFY WHY PLANS TITLE BLOCK CALL FOR
 GARAGE/APARTMENT ADDITION. THERE IS NOT GARAGE OR
 APARTMENT SHOWN ON PLANS. SEC. 107.2.1 CITY AMENDMENTS
 TO FBC. REVISE AS REQUIRED.
  
 5- ROOM ADJACENT TO THE PROPOSED ADDITION WAS A BEDROOM
 NOT STORAGE. THIS ROOM NEEDS:
 A) EGRESS AS REQUIRED BY SEC. R310 OF 2010
 FBC-RESIDENTIAL.
  
 B) LIGHT, VENTILATION AND HEATING AS REQUIRED BY SEC.
 R303 OF 2010 FBC-RESIDENTIAL.
  
 6-SPECIFY THE NAME OF THE LONG ROOM ADJACENT TO THE
 ROOM CALLED "EXISTING STORAGE/CLOSET". SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 7- SPECIFY HOW PROVIDING HEATING TO THE NEW ADDITION.
 SEC. R303.8 OF 2010 FBC-RESIDENTIAL.
  
 8- SHEET A-1:
 A) REVISE ROOF SHEATHING NAILING SPECIFICATIONS ON EAST
 AND WEST WALL DETAILS. NEED TO SPECIFY MIN. 8D RING
 SHANK NAILS AT 6" O.C ON ROOF ZONES 1 AND 2. AND, MIN.
 8D RING SHANK NAILS AT 4"O.C. IN ROOF ZONE 3. SEC.
 R803.2.3.1 OF 2010 FBC-RESIDENTIAL.
  
 B) EAST WALL DETAIL. SPECIFY ROOF VENTILATION SIZE.
 SEC. R806 OF 2010 FBC-RESIDENTIAL. NOTE: NEED TO
 PROVIDE CROSS VENTILATION.
  
 C) REQUIRED ROOF SLOPE IS 1/4" PER FT. SEC. R905.11.
 NEED TO REVISE THE DIMENSIONS SHOWN ON THE EXTERIOR
 ELEVATIONS TO ALLOW ENOUGH DROP TO ALLOW THE 1/4 PER FT
 RATIO. FOR EXAMPLE A DROP OF 4" FROM 11'-0" TO 10'-8"
 DOESN'T WORK FOR THE 22'-2" DISTANCE SHOWN ON THE ROOF
 PLAN.
  
 D) CLARIFY ON FLOOR PLAN WHERE IS THE ENTRY FOR THIS
 HOUSE. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 9- SHEET S-1:
 A) REVISE ROOF SHEATHING SPECIFICATIONS. SEE ITEM 8(A)
 ABOVE.
  
 B) REVISE TOP OF BEAM DIMENSIONS ON THE EXTERIOR
 ELEVATIONS. SEE ITEM 8(C) ABOVE.
  
 C) REVISE THE WINDOWS/DOOR DESIGN PRESSURES SHOWN ON
 THE EXTERIOR ELEVATIONS TO MATCH DESIGN PRESSURES SHOWN
 ON CHART UNDER THE WIND DESIGN CRITERIA. SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 D) ROOF FRAMING PLAN: (1) REVISE THE ROOF SHEATHING
 SPECS. SEE ITEM 8(A) ABOVE. (2) SPECIFY RAFTERS SIZE
 AND SPACING. SEC. 107.2.1 CITY AMENDMENTS TO FBC. (3)
 REVISE THE ROOF UPLIFT DESIGN PRESSURES FOR ZONE 2 AND
 3. SEE NOTE (A) OF TABLE R301.2.(2) OF 2010
 FBC-RESIDENTIAL. (4) SPECIFY SIZE OF SOLID BLOCKING.
 REMEMBER THAT CROSS VENTILATION IS REQUIRED. IF THE
 BLOCKING SIZE IS THE SAME AS THE ROOF RAFTERS, THEN
 CROSS VENTILATION IS BLOCKED ALSO.
  
 E) FOUNDATION DETAIL: SPECIFY FOOTING DEPTH BELOW
 FINISH GRADE. SEC. R403.1.4.
  
 F) ENGINEER OF RECORD TO PROVIDE ALL THE INFORMATION
 REQUIRED BY SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE
 CODE AND CHAPTER 471 FLORIDA STATUTE. INCLUDE THE
 ENGINEER'S NAME, LICENSE NUMBER, CERTIFICATE OF
 AUTHORIZATION NUMBER.
  
 10- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) EXTERIOR DOOR. PROVIDE THE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPOND TO DRAWINGS SUBMITTED. IF
 THERE IS NONE, THEN MANUFACTURER MAY APPLY FOR LOCAL
 PRODUCT APPROVAL.
  
 B) SINGLE HUNG WINDOWS. ALSO, NEED THE FLORIDA PRODUCT
 APPROVAL COVER PAGE.
  
 C) FLAT ROOF. CLEARLY IDENTIFY APPROVED ASSEMBLY TO BE
 INSTALLED TO VERIFY THE DESIGN PRESSURES OF SEC.
 R301.2.1.4.3. AND, PROVIDE THE SIGNED AND SEALED RAS
 117 CALCULATIONS IF PRODUCT APPROVAL SUBMITTED REQUIRES
 THEM TO BE SIGNED AND SEALED.
  
 D) PRECAST LINTELS AS SPECIFIED ON WALL SECTIONS.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED BY THE
 ENGINEER OF RECORD. PROVIDE ONLY THE COVER PAGE AND
 PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  