2013-03-29 17:12:40 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- PROVIDE ENERGY CALCULATIONS (2 COPIES). SEC. 103.2 |
| OF 2010 FBC-ENERGY CONSERVATION. |
| |
| 2- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. |
| SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION TO INCLUDE |
| ALL THE LABOR, MATERIALS, ALL DESIGN PROFESSIONAL FEES |
| AND OVERHEAD AND PROFIT. VALUE WAS UPDATED TO $43,843. |
| PERMIT FEE BALANCE IS $1216.11. |
| |
| 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT |
| FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY |
| OF PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY |
| IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| CODE. |
| |
| 4- CLARIFY WHY PLANS TITLE BLOCK CALL FOR |
| GARAGE/APARTMENT ADDITION. THERE IS NOT GARAGE OR |
| APARTMENT SHOWN ON PLANS. SEC. 107.2.1 CITY AMENDMENTS |
| TO FBC. REVISE AS REQUIRED. |
| |
| 5- ROOM ADJACENT TO THE PROPOSED ADDITION WAS A BEDROOM |
| NOT STORAGE. THIS ROOM NEEDS: |
| A) EGRESS AS REQUIRED BY SEC. R310 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| B) LIGHT, VENTILATION AND HEATING AS REQUIRED BY SEC. |
| R303 OF 2010 FBC-RESIDENTIAL. |
| |
| 6-SPECIFY THE NAME OF THE LONG ROOM ADJACENT TO THE |
| ROOM CALLED "EXISTING STORAGE/CLOSET". SEC. 107.2.1 |
| CITY AMENDMENTS TO FBC. |
| |
| 7- SPECIFY HOW PROVIDING HEATING TO THE NEW ADDITION. |
| SEC. R303.8 OF 2010 FBC-RESIDENTIAL. |
| |
| 8- SHEET A-1: |
| A) REVISE ROOF SHEATHING NAILING SPECIFICATIONS ON EAST |
| AND WEST WALL DETAILS. NEED TO SPECIFY MIN. 8D RING |
| SHANK NAILS AT 6" O.C ON ROOF ZONES 1 AND 2. AND, MIN. |
| 8D RING SHANK NAILS AT 4"O.C. IN ROOF ZONE 3. SEC. |
| R803.2.3.1 OF 2010 FBC-RESIDENTIAL. |
| |
| B) EAST WALL DETAIL. SPECIFY ROOF VENTILATION SIZE. |
| SEC. R806 OF 2010 FBC-RESIDENTIAL. NOTE: NEED TO |
| PROVIDE CROSS VENTILATION. |
| |
| C) REQUIRED ROOF SLOPE IS 1/4" PER FT. SEC. R905.11. |
| NEED TO REVISE THE DIMENSIONS SHOWN ON THE EXTERIOR |
| ELEVATIONS TO ALLOW ENOUGH DROP TO ALLOW THE 1/4 PER FT |
| RATIO. FOR EXAMPLE A DROP OF 4" FROM 11'-0" TO 10'-8" |
| DOESN'T WORK FOR THE 22'-2" DISTANCE SHOWN ON THE ROOF |
| PLAN. |
| |
| D) CLARIFY ON FLOOR PLAN WHERE IS THE ENTRY FOR THIS |
| HOUSE. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| |
| 9- SHEET S-1: |
| A) REVISE ROOF SHEATHING SPECIFICATIONS. SEE ITEM 8(A) |
| ABOVE. |
| |
| B) REVISE TOP OF BEAM DIMENSIONS ON THE EXTERIOR |
| ELEVATIONS. SEE ITEM 8(C) ABOVE. |
| |
| C) REVISE THE WINDOWS/DOOR DESIGN PRESSURES SHOWN ON |
| THE EXTERIOR ELEVATIONS TO MATCH DESIGN PRESSURES SHOWN |
| ON CHART UNDER THE WIND DESIGN CRITERIA. SEC. 107.2.1 |
| CITY AMENDMENTS TO FBC. |
| |
| D) ROOF FRAMING PLAN: (1) REVISE THE ROOF SHEATHING |
| SPECS. SEE ITEM 8(A) ABOVE. (2) SPECIFY RAFTERS SIZE |
| AND SPACING. SEC. 107.2.1 CITY AMENDMENTS TO FBC. (3) |
| REVISE THE ROOF UPLIFT DESIGN PRESSURES FOR ZONE 2 AND |
| 3. SEE NOTE (A) OF TABLE R301.2.(2) OF 2010 |
| FBC-RESIDENTIAL. (4) SPECIFY SIZE OF SOLID BLOCKING. |
| REMEMBER THAT CROSS VENTILATION IS REQUIRED. IF THE |
| BLOCKING SIZE IS THE SAME AS THE ROOF RAFTERS, THEN |
| CROSS VENTILATION IS BLOCKED ALSO. |
| |
| E) FOUNDATION DETAIL: SPECIFY FOOTING DEPTH BELOW |
| FINISH GRADE. SEC. R403.1.4. |
| |
| F) ENGINEER OF RECORD TO PROVIDE ALL THE INFORMATION |
| REQUIRED BY SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE |
| CODE AND CHAPTER 471 FLORIDA STATUTE. INCLUDE THE |
| ENGINEER'S NAME, LICENSE NUMBER, CERTIFICATE OF |
| AUTHORIZATION NUMBER. |
| |
| 10- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) EXTERIOR DOOR. PROVIDE THE FLORIDA PRODUCT APPROVAL |
| COVER PAGE THAT CORRESPOND TO DRAWINGS SUBMITTED. IF |
| THERE IS NONE, THEN MANUFACTURER MAY APPLY FOR LOCAL |
| PRODUCT APPROVAL. |
| |
| B) SINGLE HUNG WINDOWS. ALSO, NEED THE FLORIDA PRODUCT |
| APPROVAL COVER PAGE. |
| |
| C) FLAT ROOF. CLEARLY IDENTIFY APPROVED ASSEMBLY TO BE |
| INSTALLED TO VERIFY THE DESIGN PRESSURES OF SEC. |
| R301.2.1.4.3. AND, PROVIDE THE SIGNED AND SEALED RAS |
| 117 CALCULATIONS IF PRODUCT APPROVAL SUBMITTED REQUIRES |
| THEM TO BE SIGNED AND SEALED. |
| |
| D) PRECAST LINTELS AS SPECIFIED ON WALL SECTIONS. |
| |
| E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED BY THE |
| ENGINEER OF RECORD. PROVIDE ONLY THE COVER PAGE AND |
| PAGE SHOWING THE SPECIFIED CONNECTOR. |
| |
| 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |