Plan Review Notes
Plan Review Notes For Permit 13030652
Permit Number 13030652
Review Stop E
Sequence Number 1
Notes
Date Text
2013-03-26 12:09:15 
 THE FOLLOWING NOTE WAS PLACED ON THE PLANS.
  
 WIRING IN ALL PATIENT CARE AREAS / EXAM ROOMS REQUIRES
 A SPECIFIC LISTED WIRING METHOD THAT PROVIDES REDUNDANT
 GROUNDING AND INCLUDES AN INSULATED COPPER EQUIPMENT
 GROUND. NEC 517.13
  
  